EasyManua.ls Logo

Emerson BETTIS E796 2000 M2CP - 4.2 SET (LSC) CLOSE LIMIT SWITCH; 4.3 TO SET INTERMEDIATE SWITCH (LSA OR LSB), if included.

Emerson BETTIS E796 2000 M2CP
23 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Maintenance
Part Number: E2K-402-0313, Rev. A
Mar 2013
11
Section 4: Limit Switch Setting Instructions
Limit Switch Setting Instructions
3. Line up LSO indicator: If switch rotor arrow does not line with round holes (within ±
15°) on plate as shown in g. 8a, rotate screwdriver in same direction noted in Step
1 until switch just rotates. If arrows line up as shown in g. 8b, rotate screwdriver in
the opposite direction until switch just rotates.
Figure 8
4. Re-engage the spring-loaded drive gear by rotating disengage shaft in g. 8a.
Spring loaded disengage shaft will rise.
5. IMPORTANT: to ensure limit switch gears have re-engaged properly with spring
loaded drive gear, rmly “jiggle” (rotate) all adjusting shafts with screwdriver back
and forth. Proper engagement has been made if all shafts (LSC, LSO, LSA & LSB)
will not turn with screwdriver.
4.2 SET (LSC) CLOSE LIMIT SWITCH
1. Close valve, using handwheel. During handwheel operation note rotation direc-
tion of screwdriver in LSC adjusting shaft. After valve is fully Closed, Open it three
handwheel turns to allow for coast.
2. Repeat steps 2 through 5 of LSO setting instructions with screwdriver in LSC cavity.
IMPORTANT:
jiggle” adjusting shafts.
4.3 TO SET INTERMEDIATE SWITCH (LSA OR LSB),
if included.
1. Open Valve to desired position, then repeat steps 2 thru 5 of LSO.
IMPORTANT:
jiggle” adjusting shafts.

Related product manuals