EasyManuals Logo

Emerson Control Link User Manual

Emerson Control Link
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
4 • Control Link ACC I&O Manual 026-4704 Rev 6
4 Calculating Maximum Ambient
Temperature
Figure 4-1 shows the effects of adding an external heat sink with a 0.51°C/Watt (0.92°F/Watt) rating (using
thermal grease to ensure optimum thermal conductivity). Note that the 0.51°C/Watt
(0.92°F/Watt) heat sink rating is characteristic of typical case mullions.
An external heat sink is required for heater currents (greater than) > 10Amps.
To calculate the maximum ambient temperature at which the ACC should run with an additional external
heat sink, choose a current-amperage rating that will be operating for the case (y-axis) and plot the maximum
allowed operating temperature (x-axis) on the graph. For example, with an external heat sink at 26Amps, the
maximum ambient temperature would be 40°C (149°F).
For heater current greater than 10A, the heat sink of the Control Link ACC must be securely mounted
against a large heat-conductive surface. Using thermal grease, the Control Link ACC has a metal back which
acts as a heat sink, dissipating heat from the Triac that controls the heater. The metal must be mounted against
a conductive metal surface so heat can be conducted out of the controller. Failure to secure against the case
mullion or other metal surface may cause controller overheating and shutdown.
Figure 4-1 - Ambient Temperature Calculation - additional heat sink

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Control Link and is the answer not in the manual?

Emerson Control Link Specifications

General IconGeneral
BrandEmerson
ModelControl Link
CategoryController
LanguageEnglish

Related product manuals