EasyManuals Logo

Emerson Control Link User Manual

Emerson Control Link
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
MODBUS Network and Daisy-Chaining Network Wiring and Configuration • 17
Each Control Link ACC that will use the MODBUS network must have a unique network ID. Number each
controller in sequence, starting with 1. Refer to Figure 7-14 for dip switch and jumper settings
7.4.4. Step 4: Set the Network Baud Rate and MODBUS Parity
Figure 7-14 - Control Link ACC Network ID Dip Switch/Jumper Settings
Figure 7-15 - Control Link ACC Network Baud Rate/Parity Dip Switch/Jumper
NOTE: If you are networking Control Link ACC only for purposes of sharing a dewpoint sensor, you do not
need to set a baud rate or parity. Set all dip switches or jumpers to the DOWN (OFF) position.
This will allow
the Control Link ACC to share a dewpoint sensor as long as the network is physically present and terminated
correctly. The dip switches or jumpers are only necessary for assigning a network ID for MODBUS applica-
tions.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Control Link and is the answer not in the manual?

Emerson Control Link Specifications

General IconGeneral
BrandEmerson
ModelControl Link
CategoryController
LanguageEnglish

Related product manuals