EasyManua.ls Logo

Emerson ControlWave EFM 4710A - Page 122

Emerson ControlWave EFM 4710A
306 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-6 / Service CI-ControlWave EFM
+16Vdc), you can determine the point at which the unit turns off, i.e., the point at which the
PWRGOOD LED on the SCM goes OFF (Vt-). If the value of the bulk power supply’s +6Vdc
or +12Vdc output approaches the value of Vt+ or Vt- it should be replaced by a power
supply with the correct +6V or +12V output.
JP5, JP6, JP7, JP8 & JP9
1-to-2 Installed = 12V Bulk System
2-to-3 Installed = 6V Bulk System
P1
1
1
2
JP9
JP8
JP6
JP5
JP7
1
1
1
CR27
CR26
CR25
CR24
(Red)
I DLE LED
(Red)
Sta us LEDs
TB1
Input Power
Connector
(Red)
WATC HDO G LED
TB2
RTD Inte rfa c e
Connector
P2
MVT Interface
Connector
J2
Display Intf.
Connector
1A
J2
RJ- 4 5
TB1 - 1
TB1 - 2
TB1 - 3
(+4.5/4.9Vdc to +16.0Vdc for +6V supply)
+VIN (+9.6/10.3Vdc to +16.0Vdc for +12V supply)
-VIN (Supply Ground)
Chassis Ground (CHASSIS)
SW1 = Mode Switch
Figure 3-2 - System Controller Module’s Component & LED Designations
3.3.2 LED Checks
All ControlWave EFM Modules contain light emitting diodes (LEDs) that provide
operational and diagnostic functions. A brief synopsis of the individual module LEDs is
provided as follows:
SCM: 1 IDLE LED, 1 Watchdog LED, & 6 System Status LEDs
CPUM: 2 LEDs per Comm. Port = 6
ECOM1: 2 LEDs per Comm. Port = 8
ECOM2: 2 LEDs per Comm. Port = 8
AI/OM: None
DI/OM: 1 LED per DI x 12 = 12 DI LEDs, 1 LED per DO x 4 = 4 DO LEDs
HSCM: 1 LED per HSC x 4 = 4 HSC LEDs
MI/OM: None

Related product manuals