81
Multiple Faults
Occurred
(Read)
Power Module Temp. Fold
Back Timeout
Controlled
Shutdown
N/A
Bit 3
0 = No ; 1 = Yes
AC Input Current Fold Back
Timeout
Controlled
Shutdown
N/A
Bit 4
0 = No ; 1 = Yes
Auto Config Communication
Timeout
N/A
N/A
Bit 6
0 = No ; 1 = Yes
Modbus Communication Lost
Controlled
Shutdown
N/A
Bit 7
0 = No ; 1 = Yes
Sensor 2 (Thermistor, DLT)
High Temp
Controlled
Shutdown
N/A
Bit 8
0 = No ; 1 = Yes
Board Temp High
Controlled
Shutdown
N/A
Bit 10
0 = No ; 1 = Yes
Power Module Temp High
Controlled
Shutdown
N/A
Bit 11
0 = No ; 1 = Yes
IGBT Temp High
Controlled
Shutdown
N/A
Bit 12
0 = No ; 1 = Yes
82
1st Fault
Occurred
(Read)
Compressor Phase Current
Imbalance
Immediate
Shutdown
N/A
Bit 0
0 = No ; 1 = Yes
Micro Electronic Fault or
Drive EEPROM Fault
Immediate
Shutdown
N/A
Bit 2
0 = No ; 1 = Yes
Lockout (After 10 fault occurrences*)
Motor Over Speed
Immediate
Shutdown
N/A
Bit 3
0 = No ; 1 = Yes
Sensor 1 (HP Transducer)
fault High Pressure
Sensing Low
Immediate
Shutdown
N/A
Bit 5
0 = No ; 1 = Yes
Compressor Model
Configuration Error
Immediate
Shutdown
N/A
Bit 6
0 = No ; 1 = Yes
High Pressure Sensor Type
Configuration Error
Immediate
Shutdown
N/A
Bit 7
0 = No ; 1 = Yes
83
1st Fault
Occurred
(Read)
Sensor 2 (Thermistor, DLT)
Low Temp or Open
Controlled
Shutdown
N/A
Bit 2
0 = No ; 1 = Yes
Power Module Temp Low or
Sensor Open fault
Controlled
Shutdown
N/A
Bit 5
0 = No ; 1 = Yes
Fault Limit Lockout
N/A
N/A
Bit 15
Lockout Status
0 = No ; 1 = Yes
84
Multiple Faults
Occurred
(Read)
Compressor Phase Current
Imbalance
Immediate
Shutdown
N/A
Bit 0
0 = No ; 1 = Yes
Micro Electronic Fault or
Drive EEPROM Fault
Immediate
Shutdown
N/A
Bit 2
0 = No ; 1 = Yes
Lockout (After 10 fault occurrences*)
Motor Over Speed
Immediate
Shutdown
N/A
Bit 3
0 = No ; 1 = Yes
Sensor 1 (HP Transducer)
fault High Pressure
Sensing Low
Immediate
Shutdown
N/A
Bit 5
0 = No ; 1 = Yes
Compressor Model
Configuration Error
Immediate
Shutdown
N/A
Bit 6
0 = No ; 1 = Yes
High Pressure Sensor Type
Configuration Error
Immediate
Shutdown
N/A
Bit 7
0 = No ; 1 = Yes
85
Multiple Faults
Occurred
(Read)
Sensor 2 (Thermistor, DLT)
Low Temp or Open
Controlled
Shutdown
N/A
Bit 2
0 = No ; 1 = Yes
Power Module Temp Low or
Sensor Open fault
Controlled
Shutdown
N/A
Bit 5
0 = No ; 1 = Yes
Fault Limit Lockout
N/A
N/A
Bit 15
Lockout Status
0 = No ; 1 = Yes