Page #48 background imageLoading...
Page #48 background image
1592001440 XC645CX GB r3.4 31.10.2017.docx XC645CX 48/54
Code
Description
Cause
Action
Reset
PrSH
Low
superheat
Pre-allarm
The superheat is
less than: SH<
ASH2 + ASH0 for
ASH1 time
Only warning
Automatic:
when superheat:
SH>ASH0+ASH2+1°C(2°F)
ALSH
Low
superheat
allarm
The superheat is
less than: SH<
ASH2 for ASH3
time
Regulation
depends on
ASH4:
ASH4 = no:
regulation not
affected.
ASH4 = yes:
regulation is
stopped.
Automatic:
when superheat:
SH> ASH5 + ASH2