EC2-552_65098_EN_R05.docxx  replacement for R04  1 / 4  PCN: 864923   30.07.2012 
 
 
EC2-552 Condensing Unit Controller 
Operating Instructions 
GB 
Note: This document contains  short form instructions for experienced users. 
Use last column in List of Parameters to document your  individual settlings. 
More detailed information can be found in the User Manual.  
 
The  EC2-552  has  been  designed  to  control  single  compressor  or  tandem 
compressor  condensing  units  with  a  Copeland  Scroll  Digital
TM
  compressor  and 
variable  fan  speed  control.  The  purpose  of  the  controller  is  to  maintain  suction 
pressure at a pre-defined level by modulating compressors and to keep condensing 
pressure to a minimum by varying fan motor speed.  
 
The  Alco  Controls  PT5  pressure  transmitter  (1)  senses  suction  pressure.  The 
Digital  Scroll  Compressor  (6)  operates  as  the  base  load  compressor.  Capacity 
modulation is achieved by temporarily unloading the compressors scroll sets with 
the  Pulse  Width  Modulated  (PWM)  signal  (11)  which  controls  the  compressor 
unloading  valve  (12).  In  tandem  compressor  condensing  units,  the  single  stage 
compressor  (7)  will  only  be  turned  on  when  demand  exceeds  the  refrigeration 
capacity of the Digital Scroll Compressor. The discharge temperature thermistor of 
the Digital Scroll Compressor should be connected to the Disch. Temp. input (5) of 
the controller and the volt-free digital inputs (3) and (4) should be connected to the 
serial alarm loops of both compressors for feedback of compressor tripping. 
 
 
            setpoint          pressure 
2  control  loops  with  the  same  suction  pressure  setpoint  P0  modulate  the 
compressors. The  dead  band  control loop  with  dead  band  P1 switches the single 
stage compressor on or off, whereas a PI control loop modulates the Digital Scroll 
base load compressor between approximately 10% and 100% capacity. Being the 
base  load  compressor,  the  Digital  Scroll  Compressor  will  never  be  switched  off 
while the single stage compressor remains on. 
The PT5 pressure transmitter (2) senses condensing pressure and feeds the signal 
into  a  control  loop  which  generates  a  0…10V  output  signal  (10)  to  modulate 
condenser  fan  motor  speed  by  using  the  Alco  Controls  FSP  Fan  Speed  Power 
Module. The control algorithm for condensing pressure is generating a proportional 
transfer characteristic: 
 
 pressure 
P0 is the condensing pressure setpoint for the fan. P1 is the proportional pressure 
band within the fan speed is controlled proportional. 
!
  Safety instructions:  
• 
Read  installation  instructions  thoroughly.  Failure  to  comply  can  result  in 
device failure, system damage or personal injury. 
• 
The  product  is  intended  for  use  by  persons  having  the  appropriate 
knowledge and skills.  
• 
Ensure electrical ratings per technical data are not exceeded.  
• 
Disconnect all voltages from system before installation. 
• 
Keep temperatures within nominal limits.  
• 
Comply with local electrical regulations when wiring 
 
Technical data: 
Power supply  24VAC ±10%; 50/60 Hz; Class II 
Power consumption  20VA max. 
Communication  TCP/IP Ethernet 10MBit/s 
Plug-in connector size  Removable screw terminals 
wire size 0.14 … 1.5 mm
2
 
Temperature   
     storage 
     operating 
   -20 … +65°C 
  0 … +60°C 
Humidity     0 … 80% rh. non condensing 
Protection class  IP65 (front protection with gasket) 
Pressure transmitter inputs
24VDC, 4…20mA 
Digital inputs  Volt free contacts 5V/0,1mA 
Variable fan speed output  0…10V, 3mA max 
Triac output  24VAC 0,1…1A 
Output relays  SPDT contacts, AgCdO 
Inductive (AC15) 250V/2A 
Resistive (AC1) 250V/8A; 12A total return current
Marking 
   
Mounting 
The EC2-
552 can be mounted in panels with a 71 x 
29  mm  cutout.  See dimensional drawing below for 
space requirements including rear connectors. 
Push controller into panel cutout.(1) 
Make  sure  that  mounting  clamps  are  flush  with 
outside of controller housing 
Insert  allen  key  into  front  panel  holes  and  turn 
clockwise. Mounting clamp will turn and  gradually 
Turn allen key until mounting clamp barely touches 
panel. Then move other mounting clamp to the same 
position (3) 
Tighten both  sides 
very carefully until controller is 
secured.  Do  not  over  tighten  as  mounting  clamps 
Refer  to  the  electrical  wiring  diagram 
(right) for electrical connections. A copy of 
this diagram is labelled on the controller. 
Use  connection  wires/cables  suitable  for 
90°C operation (EN 60730-1) 
EC2  analog  inputs  are  for  dedicated 
to  any  other  devices.  Volt  free  digital 
inputs  should  only  be  connected  to  serial 
control loops or relays with gold contacts. 
They should not be connected to any other devices 
Important: Keep controller and sensor wiring well separated from mains wiring. 
Minimum recommended distance 30mm. 
Warning:  Use  a  class  II  category  transformer  for  24VAC  power  supply  (EN 
60742). Do  not  ground the 24VAC lines.  We recommend  to use one transformer 
per  EC2  controller  and  to  use  separate  transformers  for  3
rd
  party  controllers,  to 
avoid possible interference or grounding problems in the power supply. Connecting 
any EC2 inputs to mains voltage will permanently damage the EC2.