OI_EC2-XC645CX_A1_A2L_A3_EN_Rev01_866933.docx EC2-XC645CX 51/54
CODE VALUE MENUE DESCRIPTION RANGE
d3d 0 Pr2
Digital input delay for i3F = oA1
& Co2
0 - 255 s
d4d 0 Pr2
Digital input delay for i4F = oA1
& Co2
0 - 255 s
d5d 0 Pr2
Digital input delay for i5F = oA1
& Co3
0 - 255 s
did 20 Pr2
Liquid level alarm, signalling
delay
0 - 255 min.
External alarm, signalling delay:
ALMr no Pr2
Manual reset for compressor/fan
alarms
no, yES
dEU tMP Pr2
Displaying measurement unit:
pressure or temperature
tMP, PrS
CF °C Pr2
Measurement unit for
temperature
°C - °F
Measurement unit for pressure
rES dE Pr2
Resolution for display and
parameters
in, dE
dEU1 tPr Pr2
Upper display: pressure or
temperature selection
tMP - PrS
dSP2 P2 Pr2
Lower display: pressure or
temperature selection
Nu, P1, P2, P3, P4, StC1, StC2,
SEtF
dEU2 tPr Pr2
Lower display: pressure or
temperature selection
tMP, PrS
Pbd 5.0 Pr2
compressors regulation,
0.1 - 10.0 bar; 1 - 150 PSI
rS 0.0 Pr2
Band offset, suction 1
-12.0 - 12.0°C;-20 - 20 °F
-12.0 - 12.0 bar; -200 - 200 PSI;
dGSP no Pr2
Digital compressor always
activated as first compressor
no, yES
Digital input valve on at start up
Cycle time for digital compressor
PM 30 Pr2
Minimum capacity for digital
compressor
10 – PMA (dGty = ScrL)
0 – PMA (dGty = StrM)
PMA 100 Pr2
Maximum capacity for digital
compressor
PM - 100
ton 60 Pr2
Time with digital compr. at PMA
value before starting a load
0 – 255 s
toF 30 Pr2
Time with digital compr. at PM
before turning off a load
0 – 255 s
MinP 0 Pr2
Minimum capacity threshold to
start the safety lubrication
0 - 100
tMin 180 Pr2
Max time at MinP to start the
safety lubrication function
1 – 255 min.
tMAS 3 Pr2
compressor to restore the right
1 – 255 min.
ESC 0.0 Pr1
Energy saving for compressors
regulation
-50.0 - 50.0°C; -90 - 90°F
-20.0 - 20.0 bar; -300 – 300 PSI;
OnOn 5 Pr2
switching on of the same
0 - 255 min.