OI_EC2-XC645CX_A1_A2L_A3_EN_Rev01_866933.docx EC2-XC645CX 53/54
CODE VALUE MENUE DESCRIPTION RANGE
dLH 15.0 Pr2
DLT high temperature alarm
differential for recovery
0.1- 25.5°C; 1 - 50°F
dtLi nP Pr2
Probe selection for DLT control nP, P3, P4, P5
dtLP 50 Pr2
Digital Compressor Capacity
percentage in case of discharge
0 – 80 %
dtLF YES Pr1
Compressors OFF in case of
discharge line temperature alarm
no, yES
LAF 0.0 Pr1
Low pressure alarm set (fan)
-50.0 – HAF°C; -58 – HAF°F;
FA04 – HAF bar, PSI, kPa
HAF 60.0 Pr1
High pressure alarm set (fan)
LAF - 150.0 °C LAF – 302°F;
LAF - FA20 bar, PSI, kPa
HFc YES Pr2
Compressor off with high
pressure (temperature) alarm
no, yES
HFdP 50 Pr2
Digital Compressor Capacity
percentage in case of high
pressure (temperature) alarm
0 - 80 %
dHF 5 Pr2
Interval between 2 compressors
turning off with high pressure
1 - 24 s
PnF 5 Pr2
Fan pressure switch maximum
activations
0 - 15
PiF 60 Pr2
Fan pressure switch activations
time
0 - 255 min.
ASH0 5.0 Pr2
Differential for superheat warning
1
0.1 - 30.0°C; 1 - 60°F
Superheat suction alarm 1 set
Superheat suction alarm 1 delay
ASH4 no Pr2
Compressors turning off for
suction Superheat alarm 1
no, yES
ASH5 5.0 Pr2
Differential for regulation
restart for suction Superheat
0.1 - 15.0°C; 1 - 30°F
ASH6 1 Pr2
Regulation restart delay after
superheat>ASH2+ASH5
0 - 255 min.
ASH7 30.0 Pr2
Superheat 1 value for valve 1 hot
gas injection
0.1 - 30.0°C; 1 - 60°F
Probe for superheat managing
dSEP nP nP
Dynamic Set point function
enabled
nP, P3, P4
dSES 35.0 35.0
External temperature set for
DYNAMIC SET POINT function
-50.0 - 150.0°C; -58 - 302°F
dSEb -20.0 -20.0
Proportional band DYNAMIC
SET POINT
-50.0 - 50.0°C; -90 - 90°F
dSEd 5.0 5.0
Differential for DYNAMIC SET
POINT
-50.0 - 50.0 °C; -90 - 90°F;
-20.0 - 20.0 bar; -300 – 300 PSI
Analogue output 1 working mode
InCP no no
Frequency compressor always
starts at first
no, yES
AOP nP nP
Reference probe 1 analogue
output (only function FREE)
nP(0), P3(1), P4(2)