OI_EC2-XC645CX_A1_A2L_A3_EN_Rev01_866933.docx EC2-XC645CX 49/54
Parameters Default values
CODE VALUE MENUE DESCRIPTION RANGE
StC1
-10.0
Pr1
Set point for compressors
LSE, HSE
SEtF
30.0
Pr1
Set point for fans
LSF, HSF
OA1 dGS Pr2
Load 1 configuration
Nu, CPr1, CPr2, StP, dGS, 6dG,
dGSt, InC1, InC2, Fan, InF, Lin,
ALr, Liq, HGi
OA2 CPr1 Pr2
Load 2 configuration
Nu, CPr1, CPr2, StP, dGS, 6dG,
dGSt, InC1, InC2, Fan, InF, Lin,
ALr, Liq, HGi
OA3 FAn Pr2
Load 3 configuration
Nu, CPr1, CPr2, StP, dGS, 6dG,
dGSt, InC1, InC2, Fan, InF, Lin,
ALr, Liq, HGi
OA4 FAn Pr2
Load 4 configuration
Nu, CPr1,CPr2, StP, dGS, 6dG,
dGSt, InC1, InC2, Fan,InF, Lin, ALr,
Liq, HGi
OA6 ALr Pr2
Load 6 configuration
Nu, CPr1, CPr2, StP, dGS, 6dG,
dGSt, InC1, InC2, Fan, InF, Lin,
ALr, Liq, HGi
dGty SCrL Pr2
Kind of digital compressor: Scroll
or Stream
SCrL, StrM
StP
OP
Pr2
Valve output polarity
OP, CL
FtyP r448 Pr2
Refrigerant gas type
r22 = R22 134 = R134
404 =R404A 407A = R407A
407C = R407C 407F = R407F
410 = R410 507 = R507
CO2 = R744 CO2
r32 = R32 290 = R290
448 = R448A 449 = R449A
450 = R450A 452 = R452A
513 = R513 1234 = R1234ze
Sty
YES
Pr2
Compressor Sequence type
no, yES
rot
YES
Pr2
Fan Sequence type
no, yES
P1C Cur Pr2
P1 probe setting
(420 mA, 0 – 5 V, ntc)
nP, Cur, tEn, ntc
PA04 -0.5 Pr2
4 mA or 0.5 V readout for P1
probe
-1.0 - PA20 bar;
-15 - PA20 PSI;
-100 - PA20 kPa
PA20 11.0 Pr2
20 mA or 4.5V readout for P1
probe
PA04 - 61.0 bar;
PA04 - 885 PSI;
PA04 - 6100 kPa
CAL 0.0 Pr2
P1 probe offset
-12.0-12.0°C; -20-20°F;
-12.0-12.0 bar;
-200-200 PSI;
-999-999 kPA
P2C Cur Pr2
P2 probe setting
(420 mA, 0 - 5 V, ntc)
nP, Cur, tEn, ntc
FA04 0.0 Pr2
4 mA or 0.5 V readout for P2
probe
-1.0 - FA20 bar;
-15 - FA20 PSI;
-100 - FA20 kPa
FA20 30.0 Pr2
20 mA or 4.5 V readout for P2
probe
PA04 - 61.0 bar;
PA04 - 885 PSI;
PA04 - 6100 kPa
FCAL 0.0 Pr2
P2 probe offset
-12.0 - 12.0°C; -20 - 20°F;
-12.0 - 12.0 bar;
-200 - 200 PSI;
-999 - 999 kPa
P3C nP Pr2
P3 probe setting
(420 mA, 0-5 V, ntc)
np., Cur, tEn, nt10, nt86