OI_EC2-XC645CX_A1_A2L_A3_EN_Rev01_866933.docx EC2-XC645CX 54/54
CODE VALUE MENUE DESCRIPTION RANGE
LAO 0.0 0.0
Lower limit 1 analogue output
(AOF = FREE)
-50.0 - 150.0°C; -58 - 302°F
UAO 100.0 100.0
Upper limit 1 analogue output
(AOF = FREE)
-50.0 - 150.0°C; -58 - 302°F
AOM 0 0
Minimum value of analogue
output 1
0 - 100 %
AOt 0 0
Time with analogue output 1 at
max when after exceeding AOM
0 - 15 s
MPM 100 100
Maximum % variation per
minute, analogue output 1
nu, 1 - 100 %
SAO 50 50
Percentage of analogue output 1
in case of probe failure
0 - 100 %
AOH 70 70
Maximum analogue output 1
percentage when silence mode
function is enabled
0 - 100 %
2AOC
Cur
Cur
Analogue output 2 working mode
Cur, tEn
2AOF
nu
nu
Analog output 2 function
Nu, InC1, InC2, InF
2AOP nP nP
Reference probe 2nd analogue
output
nP(0), P3(1), P4(2)
2LAO 0.0 0.0
Lower limit 2 analogue output
(AOF = FREE)
-50.0 - 150.0°C; -58 - 302°F
2UAO 100.0 100.0
Upper limit 2 analogue output
(AOF = FREE)
-50.0 - 150.0°C; -58302°F
2AOM 0 0
Minimum value of analogue
output 2
0 - 100 %
2AOt 0 0
Time with analogue output 2 at
max when after exceeding AOM
0 - 15 s
2MPM 100 100
Maximum % variation per
minute, analogue output 2
nu, 1 - 100 %
2SAO 50 50
Percentage of analogue output 2
in case of probe failure
0 - 100 %
2AOH 70 70
Maximum analogue output 2
percentage when silence mode
function is enabled
0 - 100 %
tbA
YES
YES
Alarm relay silencing
no, yES
OAP
cL
cL
Polarity alarm relay
OP, CL
oFF
no
no
off function enabled
no, yES
bUr
YES
YES
Buzzer enabled
no, yES
Adr
1
Pr2
Serial address
1 - 247
rEL
3.5
Pr2
Release firmware
Readable only
SrL
-
Pr2
Sub-release firmware
Readable only
Ptb
1
Pr2
Parameter table code
Readable only
Pr2
3210
Pr1
Pr2 access
Readable only