Section 8: Hardware Fault Tolerance
The HFT of the device is 0.
The requirements of minimum hardware fault tolerance (HFT) according to Tab.6 of IEC
61511-1 have to be observed but, as long as has been performed an assessment report
fully in compliance with IEC 61508 part 1 to7, alternative fault tolerance requirements
have to be considered applicable according to Table 2 of IEC 61508-2 as per par. 11.4.5
of IEC 61511-1.