Note
- Beforeconnectingthepowersupplyconnect
alloptionsproperly(seeoptioninstructions).
- Groundproperly.
- Whensupplyingthreephasecurrentconnect
amaximumofthreewires,twophasesand
earth.
- Useandmountcableglandsorblindplugsas
requiredbynationalorlocallegislation.
- WhenIP65,IP67orNEMA4Xingressprotec-
tionisrequired,theelectricalentriesmustbe
ttedwithequivalentorhigherratedglands
orblindplugs.
  ATEX Installation instructions
- Seechapter1.2foruseofFlameproofELQ
actuatorsinATEXclassiedhazardousar-
eas.
  Requirement for Factory Mutual (FM)
 The24VDCpowersupplyhastobeprotect-
edbyapowerlimitedcircuit(<30VDCand
max.150W).
 Warning
 Theactuatorshouldbeexternallyprotected
byafuse.
 AC:Fusemin.2.5Amp.
 DC:Fusemin.10Amp.
 Warning 
 Whenpowerissuppliedonforinstanceter-
minals,4and5(for24VDC),thentheother
terminalswilloutputtheirrespective(high)
voltage. 
6.1 Powersupplyspecication
Thepowerprintisdesignedsothatfourbasictypesofpowercanbesuppliedtotheactuator(seetable6.1
andgure6.1.1)
Table6.1 Powersupplyspecication
Terminal Voltage range Maximum current *
ELQ-100 ELQ-200  ELQ-300  ELQ-500  ELQ-800
0 - 1  115VAC(+10%/-6%)50/60Hz 1A 1A 1A 1.7A 1.7A
0 - 2  230VAC(+10%/-6%)50/60Hz 0.5A 0.5A 0.5A 0.9A 0.9A
0 - 3 400VAC(+10%/-6%)50/60Hz 0.3A 0.3A 0.3A 0.5A 0.5A
4 - 5 24VDC(+10%) 4.1A 4.3A 4A 5.3A 5.1A
*  Max. current when all options mounted and under full load.
6  CONNECTING POWER SUPPLY
Wiring dimensions for power and earth connection: Max. 2.5mm² / 14 AWG. Tightening torque: 0.8Nm / 7 in/lb.