EasyManua.ls Logo

Emerson FD113 User Manual

Emerson FD113
4 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
FD113 Oil Pressure Safety Control
FD113 Oil Pressure Safety Control
Instruction Sheet
PA-00250
June 2013
THE FLEXIBLE CONTROL
• TheFD113OilPressureSafetyControlsensestheeffectiveoil
pressuredifferentialincompressorswithpositivedisplacementoil
pumps.Ifinadequateoilpressureexists,atimedelayisenergized.
Iftheoilpressuredoesnotrecovertosafelevelswithinthetime
delaysetting,thecompressorisshutdown.Thetimedelayallows
thecompressoradequatetimetoestablishoilpressureonstart–up
andavoidsnuisanceshutdownsonpressuredropofshortduration
duringtheruncycle.
• Maximumapplicationexibilityisassuredbyprovidingan
adjustabledifferentialpressureswitchwhichcanbeadjustedto
thecompressor’sminimumrequiredoilpressureneedsandan
adjustabletimedelaywhichallowsyoutoselectthelengthof
timethecompressorrunsbelowtheminimumpressurebefore
shutdown.Theminimumpressuresettingandtimedelayvalues
speciedbythecompressormanufacturershouldbeusedwhen
installingtheFD113control.
FEATURES
• PressureRangeadjustablefrom4to65PSID.
Timerstartpressure–timerstoppressureis3PSIDabove
timerstartpressure.
• ASPDTswitchisusedinthepressureportionofthecontrol
whichallowstheadditionofa“safelight”ifdesired.
• TimerisTime–Adjustablefrom20to150seconds.
Supplyvoltage–24to240VoltAC/DC.Timingunaffectedby
voltageorambienttemperaturevariations.
• ASPDTManualResetSwitchisusedintheTimerModule.
Upontime-out,thecompressorisstoppedandanalarmcircuit
isenergized.Torestartthecompressorandde-energizethe
alarmcircuit,theresetbuttonispushed.
• AfactoryinstalledJumperallowstheFD113tobepoweredfrom
asinglepowersource.Shouldseparatecircuitsbedesiredfor
thetimerand“Lockout”switch,theJumpercanberemoved.
SAFETY INSTRUCTIONS
1. ReadallInstructionsthoroughly.Failuretocomplycanresult
incontrolfailure,systemdamageorpersonalinjury.
2. Donotusewithammoniaoronhazardousorcorrosiveuids.
3. DonotinstallinHazardousLocations.
4. Disconnectelectricalpowerbeforeinstallation.Donotreapply
poweruntilcontrolinstallationiscomplete,wiringconnections
securedandcoverisinplace.
5. Beforemakingpressurecontrolconnections,depressurize
systemandmakecertainlinesareatatmosphericpressure.
Pilot Duty Ratings: 120/240VAC
U.L.B300 360VAMaximum
CONTROL RATINGS
INSTALLATION INSTRUCTIONS–GENERAL
1. Cover Removal—Loosencoverscrew,pullcoverforward.
2. Mounting—Mountthecontrolinaprotectedareaonthe
mountingbracketoraatsurfacewithscrewsprovided.
CAUTION:Ifotherscrewsareused,use8-32screwsthat
do notpenetrateintothecontrolmorethan1/8’’.
OilPressureSafetyControlsshouldalwaysbemounted
abovetheoillevelinthecompressorcrankcase.The
capillarytubesorpressureconnectionsshouldberouted
toallowthemtobefree–drainingtothecompressor
crankcase.Thiswillpreventoillogginginthecapillary
tubesduringlowambientconditions.
3. Capillary Tube Connections:Properinstallationof
capillarytubesand/orpressurecontrollineswillinsure
atrouble–freeinstallation.WARNING:Beforemakingany
pressurecontrolconnections,depressurizesystem.Failure
todosocancausesystemdamageorpersonalinjury.
• Ifthecontrolismountedonthecompressor,alllines
mustbesecuredtothecompressorsotheydonot
vibrateindependentlyfromthecompressor.
• Ifthecontrolismountedremotefromthecompressor
anopencoiledvibrationloop,2to3coils,2to3’’
diametershouldbeprovidedbetweenthecompressor
baseandthemovingcompressor.Thelinescoming
fromthecoilshouldbesecuredtothebaseand
compressorsothecoiltakesallthevibration.Avoid
any“violinstring”runsofcontrolcapillarytubes.
• Sharpbendsorkinksmustbeavoidedinthecapillary
orpressurelines.Donotallowthelinestoruband
abradeagainstanymovingsurface.Avoidanyexcess-
ivehandlingorreformingofthecopperlinesto
minimizeworkhardeningofthecopper.
4. Electrical ConnectionsWARNING: Beforemakingany
electricalconnections,disconnectallelectricalpower.
Checkwithavoltmeterasmorethanonesourceofpower
maybesupplied.Makecertaintheloadtoconnectedis
withintheelectricalratingofthecontrol(seeTable1).
• AllwiringshouldconformtoNationalElectricalCode
and/orlocalcodes.Use14AWG or larger copper
conductors ONLY.
• Theterminalsareofaclampdesign.Loosenthe
terminalscrewswithasmallscrewdriver,insert
approximately3/8’’strippedwireandsecurelytighten.
SPECIFICATIONS – FD113ZU/ZUK
Ambient Temperature Range –5°Fto+140°F
Pressure Range–PSID–Adjustable
Timer Energize:4to65PSIDneteffectiveoilpressureon
pressuredrop.
Timer De-energize:3PSIabovetimerenergizesettingon
pressurerise.
Timer
Voltage:24to240voltsACorDC
Timing:20to150seconds–Adjustable
Maximum Over Pressure:Duringinstallationandservice,the
control’spowerelementshouldnotbeexposedtopressures
exceeding330PSIG.
NEMA CLASS I – Mount the control body in an area
protected from the weather, water or excessive moisture,
dirt, dust and corrosive or explosive atmospheres.
SPECIFICATIONS – ENCLOSURE
EmersonClimate.com/FlowControls
Question and Answer IconNeed help?

Do you have a question about the Emerson FD113 and is the answer not in the manual?

Emerson FD113 Specifications

General IconGeneral
BrandEmerson
ModelFD113
CategoryController
LanguageEnglish

Summary

FD113 Oil Pressure Safety Control Overview

The Flexible Control

Explains the FD113 Oil Pressure Safety Control's function and adjustable features for compressor oil pressure monitoring.

Features of the FD113 Control

Details the adjustable pressure range, timer function, voltage compatibility, and manual reset switch.

Safety Instructions

Provides essential safety precautions to prevent system damage, failure, or personal injury during installation and use.

Control Ratings

Lists the pilot duty ratings (U.L. B300) and voltage/VA specifications for the control.

Enclosure Specifications

Specifies the NEMA CLASS I enclosure requirement for mounting the control body in protected areas.

General Installation Instructions

Outlines general steps for cover removal, mounting, and routing capillary tubes for proper installation.

FD113ZU/ZUK Model Specifications

Details specific operating ranges, pressure settings, and timer specifications for the FD113ZU/ZUK models.

Effective Oil Pressure Definition

Effective Oil Pressure Explained

Defines effective net oil pressure as the difference between oil pump and crankcase pressure, with an example.

Control Calibration and Adjustment

Manufacturer Setting Specifications

Provides typical time delay and pressure settings for various compressor manufacturers like Copeland, Bitzer, and Carrier.

Checking and Adjusting Pressure

Details the procedure for checking and adjusting the pressure setting disc to achieve desired timer start pressure.

Checking and Adjusting Timer

Explains how to check and adjust the timer to achieve the desired trip-out time for compressor shutdown.

FD113 Installation and Wiring

Pressure Connections

Instructs on connecting the 'Oil' and 'Low' pressure elements to the compressor's oil pump and crankcase connections.

Electrical Wiring Cross-Reference

Provides a cross-reference for wiring when replacing other control brands and illustrates terminal connections.

Control Checkout Procedures

Timer Checkout Procedure

Details the procedure to test the timer function by energizing the circuit and observing the compressor shutdown time.

Pressure Checkout Procedure

Explains how to accurately check the operating pressure of the FD113 control after installation.

FD113 Mounting Dimensions

Wiring Diagrams and Configurations

New Copeland 3-Wire Wiring

Illustrates wiring for a new Copeland 3-wire setup, addressing nuisance trips from auxiliary devices.

3-Wire Separate Power Source Wiring

Details wiring for a 3-wire control using a separate power source, ensuring consistent voltage for all components.

4-Wire Common Power Wiring

Presents a 4-wire wiring configuration where the control power is common to the compressor, suitable for 208/240V systems.

Related product manuals