EasyManua.ls Logo

Emerson Fisher 4200 Series - Page 5

Emerson Fisher 4200 Series
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4200 Series Transmitters
Instruction Manual
Form 5596
July 2005
5
Table 5. Hazardous Area Classifications for North America
CERTIFICATION
BODY
MODEL/
TYPE
CERTIFICATION OBTAINED ENTITY RATING
TEMPERATURE
CODE
ENCLOSURE
RATING
4211, 4221
(Intrinsic Safety)
Class/Division
SClass I,II,III Division 1 GP A,B,C,D,E,F,G
per drawing 20B6503
− − −
TC3 (T
amb
71°C)
4X
CSA
4210, 4211,
4212, 4215,
4220, 4221,
4222
(Explosion Proof)
Class/Division
SClass I, Division 1 GP C,D
− − −
T5 (T
amb
71°C)
4X
4210, 4211,
4212, 4215,
4220, 4221,
4222
Class II Division 1 GP E,F,G
T5 (T
amb
71°C)
4X
4211, 4221
(Intrinsic Safety)
Class/Division
SClass I,II,III Division 1 GP A,B,C,D,E,F,G
per drawing 20B6408
V
max
= 40 Vdc
I
max
= 200 mA
C
i
= 5 nF
L
i
= 0 mH
T4A (T
amb
71°C)
4X
FM
4210, 4211,
4212, 4215,
4220, 4221,
4222
(Explosion Proof)
Class/Division
SClass I, Division 1 GP C,D
− − −
T5 (T
amb
71°C)
4X
4211, 4221 Class I Division 2 GP A,B,C,D − − −
T5 (T
amb
71°C)
4X
4210, 4211,
4212, 4215,
4220, 4221,
4222
Class II Division 1 GP E,F,G − − −
T5 (T
amb
71°C)
4X
Table 6. Hazardous Area Classifications for Europe and Asia-Pacific
CERTIFICATE
(AGENCY)
MODEL/
TYPE
CERTIFICATION OBTAINED ENTITY RATING
TEMPERATURE
CODE
ENCLOSURE
RATING
ATEX
(LCIE)
4211, 4221
(Intrinsic Safety)
II 1 G
Gas
SEEx ia IIC T4/T5
Dust
ST81C (T
amb
71°C)
U
i
= 30 Vdc
I
i
= 150 mA
P
i
= 1.0 W
C
i
= 5 nF
L
i
= 0 mH
T4 (T
amb
71°C)
T5 (T
amb
40°C)
IP66
ATEX
(LCIE)
4211, 4221
(Type n)
II 3 G
Gas
SEEx nL IIC T4
Dust
ST81C (T
amb
71°C)
− − −
T4 (T
amb
71°C)
IP66

Related product manuals