Type 92S
10
  12.  The pressure setting of the regulator is 
    determined by:
    •  The pilot control spring adjustment on a 
       standard pilot, or
    •  The pressure-loading device in conjunction 
       with the control spring adjustment on a pressure-
       loaded pilot.  In both cases, check these settings 
       to make sure they are correct for the application.
Startup and Adjustment
Note
The maximum inlet pressure for a 
specic construction is stamped on the 
main valve nameplate. Use pressure 
gauges to monitor upstream and 
downstream pressures during startup.
Adjustment
On a regulator with any kind of Type 6492L, 
6492H, or 6492HT pilot, loosen the hex nut (key 16, 
Figure 4). Turn the adjusting screw (key 15, Figure 4) 
into the spring case to increase the downstream 
pressure.  Turn the adjusting screw out of the spring 
case to decrease the downstream pressure.  When the 
required downstream pressure is maintained for several 
minutes, tighten the hex nut to lock the adjusting screw 
in position.
On a regulator with a pressure-loaded Type 6492L, 
6492H, or 6492HT pilot, also refer to the instruction 
manual of the pressure-loading device for downstream 
pressure adjustment procedures.  Make sure that the 
combined pilot control spring setting pressure and 
spring case loading pressure do not exceed 25 psig 
(1,7 bar) for the Type 6492L pilot, 150 psig (10 bar) for 
the Type 6492H pilot, or 25 psig (17,2 bar) for the 
Type 6492HT. For example, a 5 psig (0,34 bar) spring 
setting and a 10 psig (0,69 bar) pressure loading result in 
a regulator pressure of 15 psig (1,0 bar).
Safety Override Pilot Startup 
and Adjustment
  1.  Loosen adjusting screws of the Type 6492HM 
    (or 6492HTM) safety override pilot and Type 6492H 
     (or 6492HT) intermediate pilot on the upstream 
     valve until there is no spring load. The screws 
    should turn freely by hand.
  2.  Loosen the adjusting screw of the Type 6492H 
    (or 6492HT) pilot on the downstream valve until 
    there is no spring load.
  3.  Tighten the Type 6492HM (or 6492HTM) safety 
    override pilot of the upstream valve all the way in to 
    its highest spring setting.
  4.  Tighten the Type 6492H (or 6492HT) pilot of 
     the upstream valve all the way in to its highest 
    spring setting.
  5.  Tighten the Type 6492H (or 6492HT) pilot 
     of the downstream valve to the desired 
    downstream pressure.
  6.*  Loosen the Type 6492H (or 6492HT) intermediate 
        pilot on the upstream valve to the desired      
        intermediate pressure (normally 50% of 
        inlet pressure).
  7.  Loosen the Type 6492HM (or 6492HTM) safety 
    override pilot of the upstream valve until there is no 
    spring load.
  8.  Tighten the Type 6492H (or 6492HT) pilot of the 
     downstream valve all the way in to its highest 
    spring setting.
  9.  Tighten the Type 6492HM (or 6492HTM) safety 
    override pilot of the upstream valve to desired 
    pressure as specied per ASME Boiler and 
    Pressure Vessel Code, section VIII.
  10.*  Loosen the Type 6492H (or 6492HT) pilot of the 
          downstream valve to the desired downstream
          pressure setpoint.
Startup with New Regulator Installation
  1.  Remove all pilot control spring compression by 
    turning the adjusting screw out of the spring case 
    according to the adjustment procedure.
  2.  Slowly open the upstream block valve.
  3.  Open the downstream block valve.
  4.  Open the control line shutoff valve.
Note
Before nally adjusting the pilot setting, 
allow enough time for the pilot and 
main valve to heat up and boil off any 
condensate build-up.
  5.  If a bypass is used, slowly close the bypass line  
    block valve.
  6.  Perform the adjustment procedure until the    
    downstream pressure reaches the desired setting.
* Fisher
®
 recommends establishing setpoint by tightening the adjusting screw.