Instruction Manual
D102748X012
DLC3010 Digital Level Controller
Configuration
May 2018
53
Figure 4‐8. PV HiHi Alerts
24
22
20
18
16
14
12
10
8
6
4
2
-2 0 2 4 6 8 10 12
24
22
20
18
16
14
12
10
8
6
4
2
PV (m)
DEVICE OUTPUT (mA)
PV (m)
DEVICE OUTPUT (mA)
PV (m)
PV (m)
DEVICE OUTPUT (mA)
DEVICE OUTPUT (mA)
PV HIHI ALERT ENABLED
HIHI THRESHOLD: 9 m
ALARM SETTING: HIGH
OUTPUT ACTION: DIRECT
RANGE: 0 TO 10 m
PV HIHI ALERT ENABLED
HIHI THRESHOLD: 9 m
ALARM SETTING: LOW
OUTPUT ACTION: REVERSE
RANGE: 10 TO 0 m
PV HIHI ALERT ENABLED
HIHI THRESHOLD: 9 m
ALARM SETTING: LOW
OUTPUT ACTION: DIRECT
RANGE: 0 TO 10 m
PV HIHI ALERT ENABLED
HIHI THRESHOLD: 9 m
ALARM SETTING: HIGH
OUTPUT ACTION: REVERSE
RANGE: 10 TO 0 m
NAMUR NE 43 HIGH ALARM LEVEL
NAMUR NE 43 LOW ALARM LEVEL
24
22
20
18
16
14
12
10
8
6
4
2
-2 0 2 4 6 8 10 12
-2 0 2 4 6 8 10 12
24
22
20
18
16
14
12
10
8
6
4
2
-2 0 2 4 6 8 10 12
NAMUR NE 43 LOW ALARM LEVEL
NAMUR NE 43 HIGH ALARM LEVEL
PLOT A PLOT B
PLOT C PLOT D
1
1
1
NOTE THAT THE LOW ALARM CURRENT CAPABILITY IS NOT NAMUR NE 43 COMPLIANT.