EasyManuals Logo

Emerson Fisher FIELDVUE DVC6200 Series Instruction Manual Supplement

Emerson Fisher FIELDVUE DVC6200 Series
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #3 background imageLoading...
Page #3 background image
Instruction Manual Supplement
D104205X012
DVC6200 Digital Valve Controllers
November 2020
3
Type n II 3 G
WARNING
Do not open while energized.
Potential electrostatic charging hazard. See warning on page 1.
Covered by Standards:
 EN 60079-0:2012 + A11:2013
 EN 60079-15:2010
DVC6200 and DVC6205 Series (HART HW1 & HW2, SIS, F
OUNDATION Fieldbus, PROFIBUS)
Ex nC IIC T5 (Ta ≤ 80°C) / T6 (Ta ≤ 75°C) Gc
Operating ambient temperature
Standard construction -40_C to +80_C,
Extreme temperature construction -52_C to +80_C
DVC6215
Ex nA IIC T4 (Ta ≤ 125°C) / T5 (Ta ≤ 95°C) / T6 (Ta ≤ 80°C) Gc
Operating ambient temperature
 -52_C to +125°C

Other manuals for Emerson Fisher FIELDVUE DVC6200 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6200 Series and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6200 Series Specifications

General IconGeneral
ManufacturerEmerson
SeriesFIELDVUE DVC6200
TypeDigital Valve Controller
Communication ProtocolHART
Operating Temperature Range-40 to 85 °C (-40 to 185 °F)
Enclosure RatingNEMA 4X, IP66
MaterialAluminum, Stainless Steel
Hazardous Area CertificationsATEX, IECEx, FM, CSA
Input Signal4-20 mA, HART
Power SupplyLoop-powered
Supply Pressure1.4 to 6.0 bar
CertificationsSIL3 capable
DiagnosticsAdvanced Valve Diagnostics