EasyManuals Logo

Emerson Fisher FIELDVUE DVC6200 Series Instruction Manual Supplement

Emerson Fisher FIELDVUE DVC6200 Series
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #4 background imageLoading...
Page #4 background image
Instruction Manual Supplement
D104205X012
DVC6200 Digital Valve Controllers
November 2020
4
Intrinsically Safe
WARNING
Potential electrostatic charging hazard. See warning on page 1.
Covered by Standards:
 EN 60079-0:2012 + A11:2013
 EN 6007911:2012
DVC6200 and DVC6205 Series (HART HW1 & HW2, SIS, F
OUNDATION Fieldbus, PROFIBUS)
II 1 GD
Ex ia IIC or IIB T4/T5/T6 Ga (see figure 1 to 5)
Ex ia IIIC Txxx°C Da (see figure 1 to 5)
Operating ambient temperature
Standard construction -40_C to +80_C,
Extreme temperature construction -52_C to +80_C
DVC6215
II 1 G
Ex ia IIC T4/T5/T6 Ga (see figure 2 and 4)
Operating ambient temperature
- 52_C Ta + 125_C
Intrinsically safe when connected per control drawing GE60771, as shown in the following figures
DVC6200 HW2, DVC6200 SIS figure 1 and 6...............................
DVC6205, DVC6205 SIS, and DVC6215 Remote Mount figure 2 and 6........
DVC6200f and DVC6200p figure 3 and 6..................................
DVC6205f, DVC6205p, and DVC6215 Remote Mount figure 4 and 6..........
DVC6200 HW1 figure 5 and 6...........................................
Special Conditions for Safe Use; Intrinsically Safe Applications
D This apparatus can only be connected to an intrinsically safe certified equipment and this combination must be
compatible as regards the intrinsically safe rules.
D For the model with aluminum body: the apparatus must not be submitted to frictions or mechanical impacts.

Other manuals for Emerson Fisher FIELDVUE DVC6200 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6200 Series and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6200 Series Specifications

General IconGeneral
ManufacturerEmerson
SeriesFIELDVUE DVC6200
TypeDigital Valve Controller
Communication ProtocolHART
Operating Temperature Range-40 to 85 °C (-40 to 185 °F)
Enclosure RatingNEMA 4X, IP66
MaterialAluminum, Stainless Steel
Hazardous Area CertificationsATEX, IECEx, FM, CSA
Input Signal4-20 mA, HART
Power SupplyLoop-powered
Supply Pressure1.4 to 6.0 bar
CertificationsSIL3 capable
DiagnosticsAdvanced Valve Diagnostics

Related product manuals