Instruction Manual Supplement
D104205X012
DVC6200 Digital Valve Controllers
November 2020
4
Intrinsically Safe
WARNING
Potential electrostatic charging hazard. See warning on page 1.
Covered by Standards:
 EN 60079-0:2012 + A11:2013
 EN 6007911:2012
DVC6200 and DVC6205 Series (HART HW1 & HW2, SIS, F
OUNDATION Fieldbus, PROFIBUS)
II 1 GD
Ex ia IIC or IIB T4/T5/T6 Ga (see figure 1 to 5)
Ex ia IIIC Txxx°C Da (see figure 1 to 5)
Operating ambient temperature
Standard construction -40_C to +80_C,
Extreme temperature construction -52_C to +80_C
DVC6215
II 1 G
Ex ia IIC T4/T5/T6 Ga (see figure 2 and 4)
Operating ambient temperature
- 52_C Ta + 125_C
Intrinsically safe when connected per control drawing GE60771, as shown in the following figures
DVC6200 HW2, DVC6200 SIS figure 1 and 6...............................
DVC6205, DVC6205 SIS, and DVC6215 Remote Mount figure 2 and 6........
DVC6200f and DVC6200p figure 3 and 6..................................
DVC6205f, DVC6205p, and DVC6215 Remote Mount figure 4 and 6..........
DVC6200 HW1 figure 5 and 6...........................................
Special Conditions for Safe Use; Intrinsically Safe Applications
D This apparatus can only be connected to an intrinsically safe certified equipment and this combination must be
compatible as regards the intrinsically safe rules.
D For the model with aluminum body: the apparatus must not be submitted to frictions or mechanical impacts.