DVC6200 Digital Valve Controllers
November 2020
6
Figure 2. ATEX Loop Schematics—FIELDVUE DVC6205, DVC6205 SIS, and DVC6215
1 SEE NOTES IN FIGURE 6
GE60771 Sheet 12 Rev. D
AUX TERMINALS
Not Used or
Not Provided
Uo = 30 VDC
Io = 21.2 mA
Po = 160 mW
Co = 55 nF
Lo = 78 mH
Ui = 30 VDC
Ii = 226 mA
Pi = 1.4 W
Ci = 50 nF
Li= 0.55 mH
AUX TERMINALS
ZONE 0, Ex ia IIC ZONE 0, Ex ia IIB ZONE 20, Ex ia IIIC
Ui = 30 VDC
Ii = 130 mA
Pi = 1.0 W
Ci = 15 nF
Li = 0.15 mH
NOTE 1, 3 1
DVC6215
ZONE 0, Ex ia IIC
REMOTE FIELD WIRING
TERMINAL BOX
Uo = 30 VDC
Io = 101 mA
Po = 757 mW
Co = 52.4 nF
Lo = 5.84 mH
Ui = 30 VDC
Ii = 101 mA
Pi = 757 mW
Ci = 15 nF
Li = 0.30 mH
T CODE
T4
T5
T6
T AMB
≤ 125_C
≤ 95_C
≤ 80_C
ZONE 0, Ex ia IIC
DVC6215
Ex ia IIC or Ex ia IIB
TERMINALS
Ex ia IIC
LOOP TERMINALS
Ex ia IIC
LOOP TERMINALS
*Li = 0.15 mH WHEN THE AUX
TERMINALS ARE NOT USED OR IF
THEY ARE NOT PROVIDED
*
ZONE 0, Ex ia IIC or Ex ia IIB
DVC6205
ZONE 20, Ex ia IIIC
MAX
SURFACE
TEMP
T91_C
T85_C
T AMB
≤ 80_C
≤ 74_C
T AMB
≤ 80_C
≤ 74_C
T CODE
T5
T6
TYPE
WITH I/O
PACKAGE
WITH I/O
PACKAGE
WITHOUT I/O
PACKAGE
WITHOUT I/O
PACKAGE
T AMB
≤ 80_C
≤ 61_C
T CODE
T5
T6
T AMB
≤ 80_C
≤ 61_C
MAX
SURFACE
TEMP
T104_C
T85_
C
HW2 - WITH OR WITHOUT I/O PACKAGE
DVC6205
FIELD WIRING
TERMINAL BOX