EasyManuals Logo

Emerson Fisher FIELDVUE DVC6200 Series Instruction Manual Supplement

Emerson Fisher FIELDVUE DVC6200 Series
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
Instruction Manual Supplement
D104205X012
DVC6200 Digital Valve Controllers
November 2020
7
Ui = 27.1 VDC
Ii = 130 mA
Pi = 880 mW
Ci = 15 nF
Li = 0.30 mH
AUX TERMINALS
AUX TERMINALS
Uo = 27.1 VDC
Io = 130 mA
Po = 880 mW
Co = 75 nF
Lo = 2.73 mH
ATEX APPROVED BARRIER
HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION
NOTE 5
1
NOTE 1, 3, 4 1
Ex ia IIC
LOOP TERMINALS
Ex ia IIB
LOOP TERMINALS
Ui = 30 VDC
Ii = 130 mA
Pi = 1.0 W
Ci = 15 nF
Li = 0.30 mH
Uo = 30 VDC
Io = 130 mA
Po = 1.0 W
Co = 546 nF
Lo = 16.93 mH
Ex ia IIC or Ex ia IIB
OUPUT TERMINALS
Ui = 28 VDC
Ii = 100 mA
Pi = 1.0 W
Ci = 15 nF
Li = 0.20 mH
ATEX APPROVED BARRIER
NOTE 1, 3, 4 1
POWER MAY BE APPLIED TO EITHER THE LOOP
TERMINALS OR OUTPUT TERMINALS OR TO
BOTH SETS OF TERMINALS AT THE SAME TIME
UNITS WITHOUT I/O PACKAGE WILL NOT HAVE
“OUTPUT TERMINALS” OR “AUX TERMINALS”
AVAILABLE FOR CONNECTION

Other manuals for Emerson Fisher FIELDVUE DVC6200 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6200 Series and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6200 Series Specifications

General IconGeneral
ManufacturerEmerson
SeriesFIELDVUE DVC6200
TypeDigital Valve Controller
Communication ProtocolHART
Operating Temperature Range-40 to 85 °C (-40 to 185 °F)
Enclosure RatingNEMA 4X, IP66
MaterialAluminum, Stainless Steel
Hazardous Area CertificationsATEX, IECEx, FM, CSA
Input Signal4-20 mA, HART
Power SupplyLoop-powered
Supply Pressure1.4 to 6.0 bar
CertificationsSIL3 capable
DiagnosticsAdvanced Valve Diagnostics

Related product manuals