Chapter 11  Specifications      71 
Liebert APM 90 Integrated Modular UPS    User Manual 
Chapter 11   Specifications 
The chapter provides the UPS specifications. 
11.1   Conformity And Standards 
The UPS has been designed to conform to the European and international standards listed in Table 11-1. 
Table 11-1 European and international standards 
Item  Specifications 
General and safety requirements for UPS used in operator 
access areas 
EN50091-1-1/IEC62040-1-1/AS 62040-1-1 
EMC requirements for UPS  EN50091-2/IEC62040-2/AS 62040-2 (C3) 
Method of specifying the performance and test 
requirements of UPS 
EN50091-3/IEC62040-3/AS 62040-3 (VFI SS 111) 
 
The product standards in this table incorporate relevant compliance clauses with generic IEC and EN standards for safety 
(IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction (IEC/EN/AS60146 
series and 60950). 
11.2   Environmental Characteristics 
Table 11-2 Environmental characteristics 
Rated power (kW) 
Item  Unit 
18  36  54  72  90 
Noise within 1m (in the 
front) 
dB  55 57 59 61 63 
Altitude m 
≤
1000, derate power by 1% per 100m between 1000m and 2000m 
Relative humidity  %RH  0 
~
 95, non condensing 
Operating temperature 
°
C
 
0 
~
 40; battery life is halved for every 10
°
C increase above 20
°
C 
Storage and transport 
temperature for UPS 
°
C -20 
~
 +70 
Recommended battery 
storage temperature 
°
C -20 
~
 +30 (20
°
C for optimum battery storage) 
Over-voltage level    Over-voltage level 2 
Pollution level    Pollution level 2 
 
11.3   Mechanical Characteristics 
Table 11-3 Mechanical characteristics 
Rated power (kW) 
Item  Unit 
18 (power module) 
90 (complete machine, power 
module excluded) 
Dimensions (W 
×
 D 
×
 H)  mm  480 
×
 645 
×
 130  600 
×
 1100 
×
 2000 
Net weight  kg  28  200 
Gross weight  kg  30  240 
Color  Black ZP7021 
Protection degree, IEC (60529)    IP20 (front door and back door open or closed)