Specifications
47
14.1 Product Warranty Registration
To register for warranty protection:
•Visit the Quick Links section of our Website at:
http://www.liebert.com
Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:
US: 800-222-5877
Outside the US: 614-841-6755
upstech@emersonnetworkpower.com
Contact Liebert Global Services at:
US: 800-LIEBERT (800-543-2378)
powertech@emersonnetworkpower.com
Table 13 External battery cabinet specifications
Model Number GXT2-288RTVBATT
Used w/ UPS Model Liebert GXT2-10000RT208
DIMENSIONS, Rack Mount, W x D x H
Unit (with bezel), in (mm) 16.93 x 25.98 x 7 (430 x 660 x 178); 4U
Shipping, in (mm) 22.64 x 33.46 x 12.40 (575 x 850 x 315)
WEIGHT lb (kg)
Unit 41.6 (18.9)
Shipping 50.6 (23)
BATTERY PARAMETERS
Type Valve-regulated, non-spillable, flame retardant, lead acid
Qty x V x Rating (2) x 12 x 12V x 9.0 AH
Battery Manufacturer / Part # Yuasa / REW 45-12 FR
Backup Time See Table 6 - Battery run times
ENVIRONMENTAL
Operating Temp +32°F to +104°F (0°C to +40°C)
Storage Temp +5°F to +122°F (-15°C to +50°C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation 50,000 ft. (15,000m) maximum
AGENCY
Safety UL 1778, c-UL Listed (suitable for computer room applications)
RFI/EMI FCC Part 15, Subpart B, Class A
Transportation ISTA Procedure 1A