EasyManua.ls Logo

Emerson Liebert GXT4-5000RT208 - Terminal Block Communication; Figure 5-1 Terminal-Block Communication Pin Layout

Emerson Liebert GXT4-5000RT208
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication
49 Liebert
®
GXT4
User Manual
5.3 Terminal Block Communication
The Terminal Block includes eight pins, as shown in Figure 5-1.
Figure 5-1 Terminal-block communication pin layout
NOTE
Programming the output voltage of the Liebert GXT4-5000RT208, GXT4-6000RT208, GXT4-
8000RT208, and GXT4-10000RT208 models to 220/110VAC automatically derates both the VA
and Watt ratings to 90% of the units ratings and programming the output voltage to 200/100VAC
automatically derates both the VA and Watt ratings to 80% of the units ratings (refer to 9.0 -
Specifications for the VA and Watt ratings)
NOTE
This program is compatible with UPS models beginning with ‘GXT4,’ as in ‘GXT4-3000RT230.’
It is not compatible with earlier versions of the Liebert GXT UPS.
A computer running Microsoft
®
Windows 2000
®
, Windows XP
®
, Windows Vista
®
, Windows 7 or
Windows 8 is required to set up and run the configuration program.
No. Description
1 Low battery warning
2 On-battery warning
3 Any mode shutdown
4 Battery mode shutdown

Table of Contents

Related product manuals