Communication
Liebert
®
GXT4
User Manual 52
Remote Emergency Power Off—GXT4-5000RT208,
GXT4-6000RT208, GXT4-8000RT208, GXT4-10000RT208
+24 V supplied
by GXT4 UPS
How UPS ships, with jumper removed
and in the accessory bag.
How UPS must be wired to operate with no repo connection.
Jumper in accessory bag must be installed.
+24 V supplied
by GXT4 UPS
+24 V supplied
by GXT4 UPS
+24 V supplied
by GXT4 UPS
How UPS must be wired to operate
with connection to a normally-closed (NC) repo connection.
Jumper in accessory bag must be removed as this wired
to a remote switch.
How UPS must be wired to operate
with connection to a normally-open (NO) repo connection.
Jumper in accessory bag must be installed.
123 4
123 4
123 4
123 4