3.6 Intelligent Paralleling
Intelligent Paralleling is intended to increase system efficiency and reduce operating hours on the
modules. Intelligent Paralleling will put one or more paralleled modules into standby operation when
the number of redundant modules is above the user specified threshold.
3.6.1 Intelligent Paralleling Setup
Operation
Enable, Disable
Default: Disabled
Minimum System Redundancy—Permits setting the redundancy threshold at which Intelligent
Paralleling will operate. This is the minimum Number of Redundant Modules that the system will
allow before bringing one or more modules back to normal operation and terminating Intelligent
Paralleling.
Min: 0; Max: Number of Modules - 1; Iteration: 1
•Default: 1
Maximum Time Module In Standby—Permits cycling a module that has had Intelligent
Paralleling active the longest with another module currently in normal operation after the selected
amount of time. After the cycle is successful, the new module that has had Intelligent Paralleling
active the longest will go into standby mode. Disable this feature by selecting 0 days.
Min: 0 Days; Max: 30 Days; Iteration: 1 Day
Default: 30 Days
Shutdown Delay—Permits choosing how long a module should wait before Intelligent Paralleling is
active and module is in standby.
Min. 5 minutes; Max. 60 minutes; Iteration 1 minute
Default: 5 minutes
Figure 55 Intelligent Paralleling settings
NOTE
These are global settings. The settings only have to be configured from one module.