66
3.6.6 Module Standby Rotation
Module Standby Rotation will limit the time a module is in standby operation when the Number of
Redundant Modules doesn't change for a long period.
The module selected as the next to terminate Intelligent Paralleling per Module Selection -
Termination, (see Intelligent Paralleling Module Termination on page 65), will not be in
standby operation for longer than Maximum Time Module In Standby (see 3.6.1 - Intelligent
Paralleling Setup).
When this time expires, the module will terminate Intelligent Paralleling and come back online.
The next module selected to activate Intelligent Paralleling will be put into standby operation.
NOTE
When Maximum Time Module In Standby setting is 0, Module Standby Rotation is disabled.