REV. 5 7/6/2007
Liebert Monitoring Group –Development
9
Static Bypass Switch
Inverter
Communication Fail 10281
Rectifier
Communication
Failure 10282
Parallel
Communication Fault
10283
Operation Fault 10289
Data Point Input Register Holding Register # of Reg. Scale Notes / Units
Number of Input
Lines 30004 40004 1 1 Bits 12 - 15
Number of Bypass
Lines 30004 40004 1 1 Bits 4 - 7
Number of Output
Lines
30004 40004 1 1 Bits 8 - 11
Number Of
SubModules
30009 40009 1
Load Circuit Present 30013 40013 1
There are 16 possible
Load Circuits. So
each bit represents 1
load circuit. Load
Circuit 1 is bit 0, Load
Circuit 2 is bit 1 and
so on. If the bit is 1
then the Load Circuit
is supported.
Module Number 30014 40014 1
Device Module Count 30015 40015 1
Device Redundant
Count 30016 40016 1
Device Module Mode 30017 40017 1
Nominal Power
Rating 30021 40021 2 VA
Nominal Input
Voltage 30027 40027 1 V
Nominal Output
Voltage
30028 40028 1 V
Nominal Static
Bypass Switch
Voltage 30029 40029 1 V
Nominal Input
Frequency 30031 40031 1 10 Hz
Nominal Output
Frequency 30032 40032 1 10 Hz
Nominal Power
Factor
30033 40033 1 100
Nominal DC Bus #1
Voltage 30035 40035 1 V
Nominal DC Bus #2
Voltage
30036 40036 1