REV. 5 7/6/2007
Liebert Monitoring Group –Development
10
Nominal Battery Float
Voltage
30038 40038 1 V
Load Bus Sync Mode 30040 40040 1
Auto Restart Delay 30051 40051 1 1 Seconds
Device Low Battery
Time 30053 40053 1 Minutes
Input Frequency 30107 1 10 Hz
Output Frequency 30108 1 10 Hz
Bypass Frequency 30109 1 10 Hz
Battery Charge
Status
30112 1
1 - 100% Charged
2 - Less than 100%
Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Voltage 30113 1 V
Battery Current
(Charge/Discharge) 30114 1 A
Data Point Register Coil # of Reg. Scale Notes / Units
Battery Time
Remaining 30115 1 Minutes
Battery Charge
Percentage
30116 1 %
Battery Temperature 30117 1 C
Ambient Temperature 30119 1 C
Parallel Load Source 30128 1
Rotary Breaker 30129 1
Battery Test Result 30130 1
1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
6 - Inhibited
Input Voltage L1-L2 30151 2 W
Input Voltage L1 30153 1 V
Input Current L1 30154 1 A
Input Power Factor
L1 30155 1 100
Bypass Voltage L1 30159 1 V
Output Voltage L1 30163 1 V
Output Current L1 30164 1 A
Output Load L1 30165 1 1
Output Power Factor
L1 30166 1 100
Apparent Output
Power L1 30168 2 VAR
Reactive Output 30170 1 %