REV. 5 7/6/2007
Liebert Monitoring Group –Development
33
Hour:Minute
Sleep Interval 2
Start Time
Hour:Minute
30042 40042 1 MSB:Hr U607(FROM)
Sleep Interval 2
End Time
Hour:Minute
30043 40043 1 MSB:Hr U607(TO)
Timer Dead Band 30044 40044 1 X10 U611
Manual VSD
Timer/Counter[6]
30045 40045 1
High
Temperature
30050 40050 1 X10 U203
Low Temperature 30051 40051 1 X10 U204
High
Temperature
Sensor A
30052 40052 1 X10 U208
Low Temperature
Sensor A
30053 40053 1 X10 U209
High Humidity 30054 40054 1 1 % U205
Low Humidity 30055 40055 1 1 % U206
High Humidity
Sensor A
30056 40056 1 1 % U210
Low Humidity
Sensor A
30057 40057 1 1 % U211
Fan Run Hour
Threshold
30070 40070 1 Hour U502
Compressor 1
Run Hour
Threshold
30071 40071 1 Hour U503
Compressor 2
Run Hour
Threshold
30072 40072 1 Hour U504
Humidifier run
hours Threshold
30073 40073 1 Hour U510
Dehumidification
run hours
Threshold
30074 40074 1 Hour U511
CW/FC run hours
Threshold
30075 40075 1 Hour U505
Electrical Heaters
#1 run hours
Threshold
30076 40076 1 Hour U507
Electrical Heaters
#2 run hours
Threshold
30077 40077 1 Hour U508
Electrical Heaters
#3 run hours
Threshold
30078 40078 1 Hour U509
Hot Water / Hot
Gas run hours
Threshold
30079 40079 1 Hour U506
Operating State
[7]
30100 - 1 -
EnvState.
OperatingState
Number of Active 30101 - - -