Chapter 1 Product Description 3
RDU-SIC G2 Card User Manual
Collecting the system information of RDU-SIC G2
1. Setting the network information such as IP, subnet mask, gateway and DNS;
2. Controlling whether the upper monitoring system (RDU-M manager) can visit the
RDU-SIC G2;
3. Remote service setting
Adding, modifying and deleting user information
Calibrating the real time clock of RDU-SIC G2
Rebooting the RDU-SIC G2 and restoring default configuration
Modifying site information online
Upgrading the application program online
Setting title and logo picture at the top of the Web page
Displaying serial number, identify code and software version, and supplying links for
downloading user manual and tool software
1.3 Technical Specifications
1.3.1 Environment Specifications
See Table 1-5 for the environment specifications of RDU-SIC G2.
Table 1-5 Environment conditions
Usually in data center or computer room, with air conditioner
5%RH ~ 95%RH, no condensing
Dust: compliant with the indoor requirements of GR-63. No corrosive gas, flammable gas, oily
mist, steam, water drops or salt
Power distribution network
1.3.2 Performance Specifications
See Table 1-6 for the performance specifications of RDU-SIC G2.
Table 1-6 Performance specifications
Connected distance
(unit: m)
Connected number /
connection point
Connecting nodes of COM ports
Standard category 4 twisted-pair cable
Three Intelligent devices
8 test points
[1]
of Sensor
Note:
[1]: The RDU-SIC G2 can connect intelligent devices through COM1 or COM2. The connected devices of single COM cascade
cannot exceed two