EasyManua.ls Logo

Emerson MICRO MOTION 1500 - Page 65

Emerson MICRO MOTION 1500
146 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration and Use Manual 57
Configuring the Filling and Dosing Application
Optional Configuration Using the FillerFiller ConfigurationUsing the Transmitter
Note: Either Open Primary or Open Secondary must be set to 0. Either Close Primary or Close
Secondary must be set to 100% (if configured by %) or 0 (if configured by quantity). Settings are
adjusted automatically to ensure that these requirements are met.
If you are configuring a three-position analog fill, configure
Open Full and Closed Partial
values (see Section 7.4.3 and Table 7-5), then click
Apply.
Figure 7-3 Filling panel
4. Configure transmitter outputs for the requirements of your filling application. Options are
listed in Table 7-1.
To configure Channel B or C as a discrete output, use the
Channel Configuration panel in
the ProLink II
Configuration window (see Section 4.6). To assign a function to Channel
B or Channel C, use the
Discrete IO panel in the ProLink II Configuration window (see
Figure 7-4).
To configure Channel A as a discrete output, use the
Analog Output panel in the
ProLink II
Configuration window (see Figure 7-5). In this panel:
-Set
Primary Variable to Primary Valve or Secondary Valve.
- Ensure that
Enable 3 Position Valve is disabled.

Table of Contents

Other manuals for Emerson MICRO MOTION 1500

Related product manuals