Chapter 4 Alarm Handling 17
NetSure 211 C45 Embedded Power Supply System User Manual
4. Hold the rectifier handle, push the new rectifier into the slot and make sure the connection is good.
After a brief delay, the rectifier RUN indicator will turn on and the fan will start running.
5. Check that the new rectifier works normally.
You should make sure that:
1) The monitoring module recognizes the new rectifier.
2) The new rectifier shares current with other rectifiers.
3) When this new rectifier is pulled out, there is a corresponding alarm and the monitoring module displays the alarm.
If the new rectifier passes all the above tests, the replacement is a success.
6. Push the handle back into the front panel to lock the rectifier.
7. Fix the fixing screw of the handle of the rectifier with a Phillips screwdriver.