108 Appendix 1 Technical And Engineering Data
Appendix 1 Technical And Engineering Data
Table 1 Technical data
Parameter
category
Parameter Description
Environmental
Operating temperature -5°C ~ 40°C
Storage temperature -40°C ~ 70°C
Relative humidity 5%RH ~ 95%RH
Altitude ≤ 2,000m (derating is necessary above 2,000m)
Others No conductive dust or erosive gases. No possibility of explosion
AC input
AC input system
NetSure 701 A51 (PS48300-3A/3200-X2): P + N + PE/ 230Vac
Others: 3P + N + PE/ 380Vac
Input voltage range
NetSure 701 A51: 85 ~ 290Vac
NetSure 501 A50, NetSure 501 AA0: 85 ~ 300Vac
Input AC voltage frequency 45Hz ~ 65Hz
Max input current
NetSure 701 A51 ≤ 103A
NetSure 501 A50 ≤ 54A
NetSure 501 AA0 ≤ 108A
Power factor ≥ 0.99
DC output
Rated output DC voltage -48Vdc
Output DC voltage -42.3Vdc ~ -57.6Vdc
Maximum output current
NetSure 701 A51 ≤ 275A, load current ≤ 200A, battery charge
current ≤ 50A
NetSure 501 A50 ≤ 150A, load current≤ 120A, battery charge
current ≤ 30A
NetSure 501 AA0 ≤ 300A, load current≤ 250A, battery charge
current ≤ 50A
Voltage set-point accuracy ≤ 1%
Efficiency
NetSure 701 A51 ≥ 89%
NetSure 501 A50, NetSure 501 AA0 ≥ 90%
Noise (peak-peak) ≤ 200Mv (0 ~ 20MHz)
Weighted noise ≤ 2Mv (300 ~ 3400Hz)
AC input alarm
and protection
AC input over-voltage alarm point Default: 280 ± 5Vac, cofigurable through monitoring module
AC input over-voltage alarm recovery
point
Default: 270 ± 5Vac, 10Vac lower than the AC input over-voltage
alarm point
AC input under-voltage alarm point Default: 180 ± 5Vac, configurable through monitoring module
AC input under-voltage alarm
recovery point
Default: 190 ± 5Vac, 10Vac higher than the AC input under-voltage
alarm point
AC input over-voltage protection point
NetSure 501 A50, NetSure 501 AA0: 305 ± 5Vac by default,
cofigurable through monitoring module
NetSure 701 A51: 295 ± 5Vac by default, cofigurable through
monitoring module
AC input over-voltage protection
recovery point
NetSure 501 A50, NetSure 501 AA0: 295 ± 5Vac by default, 10Vac
lower than the AC input over-voltage alarm point
NetSure 701 A51: 285 ± 5Vac by default, 10Vac lower than the AC
input over-voltage alarm point
AC input under-voltage protection
point
Default: 80 ± 5Vac, configurable through monitoring module
AC input under-voltage protection
recovery point
Default: 95 ± 5Vac, 10Vac higher than the AC input under-voltage
alarm point
DC output alarm
and protection
DC output over-voltage alarm point Default: 58.0 ± 0.2Vdc, configurable through monitoring module
DC output over-voltage recovery
point
Default: 57.5 ± 0.2Vdc, 0.5Vdc lower than the over-voltage alarm
point
DC output under-voltage alarm point Default: 45.0 ± 0.2Vdc, configurable through monitoring module
DC output under-voltage recovery
point
Default: 45.5 ± 0.2Vdc, 0.5Vdc higher than the under-voltage alarm
point
DC output over-voltage proteciton
point
Default: 59.0 ± 0.2Vdc, configurable through monitoring module
LLVD Default: 44.0 ± 0.2Vdc, configurable through monitoring module
BLVD Default: 43.2 ± 0.2Vdc, configurable through monitoring module
NetSure 501 A50, NetSure 501 AA0, NetSure 701 A51 19-Inch Subrack Power Supply System User Manual

Table of Contents

Other manuals for Emerson NetSure 501 AA0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson NetSure 501 AA0 and is the answer not in the manual?

Emerson NetSure 501 AA0 Specifications

General IconGeneral
BrandEmerson
ModelNetSure 501 AA0
CategoryPower Supply
LanguageEnglish

Related product manuals