108 Appendix 1 Technical And Engineering Data
Appendix 1 Technical And Engineering Data
Table 1 Technical data
Parameter
category
Parameter Description
Environmental
Operating temperature -5°C ~ 40°C
Storage temperature -40°C ~ 70°C
Relative humidity 5%RH ~ 95%RH
Altitude ≤ 2,000m (derating is necessary above 2,000m)
Others No conductive dust or erosive gases. No possibility of explosion
AC input
AC input system
NetSure 701 A51 (PS48300-3A/3200-X2): P + N + PE/ 230Vac
Others: 3P + N + PE/ 380Vac
Input voltage range
NetSure 701 A51: 85 ~ 290Vac
NetSure 501 A50, NetSure 501 AA0: 85 ~ 300Vac
Input AC voltage frequency 45Hz ~ 65Hz
Max input current
NetSure 701 A51 ≤ 103A
NetSure 501 A50 ≤ 54A
NetSure 501 AA0 ≤ 108A
Power factor ≥ 0.99
DC output
Rated output DC voltage -48Vdc
Output DC voltage -42.3Vdc ~ -57.6Vdc
Maximum output current
NetSure 701 A51 ≤ 275A, load current ≤ 200A, battery charge
current ≤ 50A
NetSure 501 A50 ≤ 150A, load current≤ 120A, battery charge
current ≤ 30A
NetSure 501 AA0 ≤ 300A, load current≤ 250A, battery charge
current ≤ 50A
Voltage set-point accuracy ≤ 1%
Efficiency
NetSure 701 A51 ≥ 89%
NetSure 501 A50, NetSure 501 AA0 ≥ 90%
Noise (peak-peak) ≤ 200Mv (0 ~ 20MHz)
Weighted noise ≤ 2Mv (300 ~ 3400Hz)
AC input alarm
and protection
AC input over-voltage alarm point Default: 280 ± 5Vac, cofigurable through monitoring module
AC input over-voltage alarm recovery
point
Default: 270 ± 5Vac, 10Vac lower than the AC input over-voltage
alarm point
AC input under-voltage alarm point Default: 180 ± 5Vac, configurable through monitoring module
AC input under-voltage alarm
recovery point
Default: 190 ± 5Vac, 10Vac higher than the AC input under-voltage
alarm point
AC input over-voltage protection point
NetSure 501 A50, NetSure 501 AA0: 305 ± 5Vac by default,
cofigurable through monitoring module
NetSure 701 A51: 295 ± 5Vac by default, cofigurable through
monitoring module
AC input over-voltage protection
recovery point
NetSure 501 A50, NetSure 501 AA0: 295 ± 5Vac by default, 10Vac
lower than the AC input over-voltage alarm point
NetSure 701 A51: 285 ± 5Vac by default, 10Vac lower than the AC
input over-voltage alarm point
AC input under-voltage protection
point
Default: 80 ± 5Vac, configurable through monitoring module
AC input under-voltage protection
recovery point
Default: 95 ± 5Vac, 10Vac higher than the AC input under-voltage
alarm point
DC output alarm
and protection
DC output over-voltage alarm point Default: 58.0 ± 0.2Vdc, configurable through monitoring module
DC output over-voltage recovery
point
Default: 57.5 ± 0.2Vdc, 0.5Vdc lower than the over-voltage alarm
point
DC output under-voltage alarm point Default: 45.0 ± 0.2Vdc, configurable through monitoring module
DC output under-voltage recovery
point
Default: 45.5 ± 0.2Vdc, 0.5Vdc higher than the under-voltage alarm
point
DC output over-voltage proteciton
point
Default: 59.0 ± 0.2Vdc, configurable through monitoring module
LLVD Default: 44.0 ± 0.2Vdc, configurable through monitoring module
BLVD Default: 43.2 ± 0.2Vdc, configurable through monitoring module
NetSure 501 A50, NetSure 501 AA0, NetSure 701 A51 19-Inch Subrack Power Supply System User Manual