12 Chapter 3 Installation Testing
OK Comments
Check the voltage, current, current limiting point of rectifiers through the monitoring module. They
should agree with the actual parameters.
For the system configured with temperature sensor, the monitoring module should be able to display
the battery ambient temperature. Hold the probe of the temperature sensor with hand and watch the
monitoring module, which should diplay the change of temperature.
3.4 Final Steps
OK Comments
Disconnect all test equipment from the system and make sure that materials irrelevant to the equipment
have been all removed.
Restore the equipment to its original condition and close the cabinet door.
Check and handover the equipment that the user has purchased.
Note down all the operations taken, including time of the operation and name of the operator.
If any defect is found in this equipment, inform the personnel responsible for the contract.
If repairing is needed, please fill in the FAILURE REPORT and send the report together with the defective unit to the
repairing center for fault analysis.
NetSure 501 A50, NetSure 501 AA0, NetSure 701 A51 19-Inch Subrack Power Supply System User Manual

Table of Contents

Other manuals for Emerson NetSure 501 AA0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson NetSure 501 AA0 and is the answer not in the manual?

Emerson NetSure 501 AA0 Specifications

General IconGeneral
BrandEmerson
ModelNetSure 501 AA0
CategoryPower Supply
LanguageEnglish

Related product manuals