Chapter 5 Use Of Monitoring Module M800D 43
With the alarm level setting of “Rectifier” as an example:
In the preceding screen, press ▲ or ▼ to move the cursor to the menu of “Rectifier” and press ENT, following screen
pops up:
Rect AC Failure
Major
Rect Over Temp
Observation
The above screen displays the alarm information of the rectifier. The information is configurable. The alarm
information is displayed in several screens, user can press ▲ or ▼ to scroll through the screens to view the alarm
information.
If user wants to change the alarm level of “Rectifier AC Failure” from “Major” to “Critical”, press ▲ or ▼ to move the
cursor to the setting of “Rectifier AC Failure”, and press ENT. At this point, this row is highlighted which indicates user
can modify the setting. User can select the alarm level of “Critical” by pressing ◄ or ►.
Method of setting alarm control:
The Alarm parameter setting is shown in the following figure.
Alarm Control
Alarm Param
Alarm Level
In the preceding screen, press ▲ or ▼ to move the cursor to the menu of “Alarm Control” and press ENT, following
screen pops up:
Alarm Voice
On
Block Alarm
Normal
Block Alarm
Normal
Clear His Alarm
Yes
Similar to modifying the alarm level, user can modify the setting of “Alarm Voice” from “On” to “Off”,”3 Min”, “10 Min”,
”1 Hour”, or ”4 Hour”.
User can also modify the setting of “Block Alarm” from “Normal” to “Blocked” or from “Blocked” to “Normal” by using
the same method.
If user executes the setting “Yes” of “Clear His Alarm” (Note: For “Clear His Alarm”, there is only one option of ”Yes”,
and there is no option of ”No”), all the history alarm will be cleared.
System parameters setting
Parameter Set
SMIO 8
Alarm Param
System Param
In the preceding screen, move the cursor “” to “System Param”, and then press ENT to set the system information
(parameters).
System information is displayed in following screens:
Language
English
LCD Time Zone
GMT
M800D supports 2 languages, one is English and another is the local language, which are configurable through
above screen. LCD Time Zone support the selection from GMT-12:00 to GMT+13:00. User can select the language in
the preceding screen.
NetSure 501 A50, NetSure 501 AA0, NetSure 701 A51 19-Inch Subrack Power Supply System User Manual

Table of Contents

Other manuals for Emerson NetSure 501 AA0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson NetSure 501 AA0 and is the answer not in the manual?

Emerson NetSure 501 AA0 Specifications

General IconGeneral
BrandEmerson
ModelNetSure 501 AA0
CategoryPower Supply
LanguageEnglish

Related product manuals