80 Chapter 5 Use Of Monitoring Module M800D
Parameter and alarm for maximum power consumption
Table 1.2 Parameter and alarm for maximum power consumption
Parameter Range Default Step change
Maximum Power
Consumption Limit Enabled
Yes/No No N/A
Battery Discharge Enabled Yes/No No N/A
Default category LED Alarm Number Alarm name
OA Y 121 Over maximum power alarm
Rectifier redundancy parameters
Table 1.3 Parameter and alarm for redundant rectifier switch ON/OFF
Parameter Range Default Step change
Rectifier Redundancy Enabled Yes/No No N/A
Min Redundancy 1 to Max Redundancy – 110 100 10
Max Redundancy 111 to 4800 300 10
Switch Off Delay 1 to 60min 5min 1min
Rectifier cycling parameters
Table 1.4 Parameter and alarm for rectifier cycling
Parameter Range Default Step change
Cycle Period 1 to 500 Days 30 1
Cycle Activation Time 0 to 23 o’clock 3 o’clock 1