EasyManuals Logo

Emerson NetSure 501 AA0 User Manual

Emerson NetSure 501 AA0
127 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #87 background imageLoading...
Page #87 background image
80 Chapter 5 Use Of Monitoring Module M800D
Parameter and alarm for maximum power consumption
Table 1.2 Parameter and alarm for maximum power consumption
Parameter Range Default Step change
Maximum Power
Consumption Limit Enabled
Yes/No No N/A
Battery Discharge Enabled Yes/No No N/A
Default category LED Alarm Number Alarm name
OA Y 121 Over maximum power alarm
Rectifier redundancy parameters
Table 1.3 Parameter and alarm for redundant rectifier switch ON/OFF
Parameter Range Default Step change
Rectifier Redundancy Enabled Yes/No No N/A
Min Redundancy 1 to Max Redundancy – 110 100 10
Max Redundancy 111 to 4800 300 10
Switch Off Delay 1 to 60min 5min 1min
Rectifier cycling parameters
Table 1.4 Parameter and alarm for rectifier cycling
Parameter Range Default Step change
Cycle Period 1 to 500 Days 30 1
Cycle Activation Time 0 to 23 o’clock 3 o’clock 1
NetSure 501 A50, NetSure 501 AA0, NetSure 701 A51 19-Inch Subrack Power Supply System User Manual

Table of Contents

Other manuals for Emerson NetSure 501 AA0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson NetSure 501 AA0 and is the answer not in the manual?

Emerson NetSure 501 AA0 Specifications

General IconGeneral
BrandEmerson
ModelNetSure 501 AA0
CategoryPower Supply
LanguageEnglish

Related product manuals