27 PACSystems™ RSTi-EP EPSCPE115 Standalone CPU Quick Start Guide GFK-3039C
5. How can I recover the controller from the Stop/Faulted state?
a) A Stop/Faulted state cannot persist through a power cycle. To recover the
controller, there are two methods:
1) Power cycle the controller
2) Perform a CLEAR operation from the PME software.
6. When should I replace the internal supercapacitor?
Whenever a Failed Battery Signal fault is logged in the controller’s fault table,
replace the internal supercapacitor by following the instructions in the section
entitled Replacement of Internal Supercapacitor.