17 PACSystems™ RSTi-EP EPSCPE115 Standalone CPU Quick Start Guide GFK-3039C
Programming the CPE115
To configure the CPE115, connect the computer running the PME programming
software to an Ethernet port of LAN1 using the default IP address 192.168.0.100. PME
9.5 SIM 1 or later is required.
Configuration will either start out using the RSTi-EP CPE115 template when creating
a new project or will convert an existing project to the CPE115 using the Family
Conversion feature in PME.
Backwards Compatibility
To convert an existing project which uses any other PLC, use the Family Conversion
feature in PME. Be aware of the constraints involved, as will be notified in PME. For
instance, the first PROFINET Controller in an RX3i CPU320 application will be assigned
to the embedded PROFINET Controller feature of the CPE115.
PROFINET Controller Configuration
An Embedded PROFINET Controller may be configured on LAN2. To enable the
PROFINET Controller in a CPE115 project, select the CPE115 target in the PME
Navigator (Figure 11) and open the Hardware Configuration.
On the Settings tab, change the LAN2 Mode of the selected port to PROFINET. The
PROFINET Controller node description then displays that a PROFINET node exists on
the selected LAN (under the CPE115). For further details, refer to the PACSystems Rx3i
& RSTi-EP PROFINET IO-Controller User Manual, GFK-2571.