12
Reference Manual
00809-0200-4802, Rev BA
Section 2: Configuration
May 2013
Configuration
2.6.3 Review radio information
To view radio information:
1. From the Home screen, choose 2: Configure.
2. Choose 2: Manual Setup.
3. Choose 9: Device Information.
4. Choose 3: Radio.
5. Select from the corresponding number to view each field:
2.7 Check output
Before performing other transmitter operations, ensure that the transmitter is operating
properly by checking the operating parameters.
2.7.1 Operating parameters
The pressure output value in both engineering units and percent of range will reflect the applied
pressure even when the applied pressure is outside of the configured range as long as the
applied pressure is between the upper and lower range limit of the transmitter. For example, if a
Range 2 3051S_T (LRL = 0 psi, URL = 150 psi) is ranged from 0 to 100 psi, an applied pressure of
150 psi will return a % of range output of 150% and an engineering output of 150 psi.
To view the Operating Parameters menu:
1. From the Home screen, select 3: Service Tools.
2. Choose 2: Variables.
Fast Keys
2, 2, 9, 3
1 Manufacturer
2 Device Type
3 Device Revision
4 Software Revision
5 Hardware Revision
Fast Keys
3, 2