30
Reference Manual
00809-0200-4802, Rev BA
Section 3: Installation
May 2013
Installation
Figure 3-2. Conduit Plug Location
Field Communicator connections
In order for the Field Communicator to interface with the Rosemount 3051S, the Power Module
must be connected.
Figure 3-3. 375 Field Communicator Connections
3.3.3 Mechanical
Note
For steam service or for applications with process temperatures greater than the limits of the
transmitter, do not blow down impulse piping through the transmitter. Flush lines with the
blocking valves closed and refill lines with water before resuming measurement.
Note
When the transmitter is mounted on its side, position the Coplanar flange to ensure proper
venting or draining. Mount the flange as shown in Figure 3-5 on page 37, keeping drain/vent
connections on the bottom for gas service and on the top for liquid service.
3.3.4 Environmental
Access requirements and cover installation on page 32 can help optimize transmitter
performance. Mount the transmitter to minimize ambient temperature changes, vibration,
mechanical shock, and to avoid external contact with corrosive materials. Appendix A:
Specifications and Reference Data lists temperature operating limits.
Conduit Plug
Conduit Plug
COMM
P/N 00753-9200-0010
COMM
COMM
P/N 00753-9200-0010
P/N 00753-9200-0010