3.2 Switch HART revision mode
If the HART Protocol configuration tool is not capable of communicating
with HART Revision 7, the transmitter will load a generic menu with limited
capability. The following procedure will switch the HART Revision mode
from the generic menu.
Procedure
Select Manual Setup Device Information Identification Message.
a) To change to HART Revision 5, enter HART5 in the Message field.
b) To change to HART Revision 7, enter HART7 in the Message field.
Function HART 5 Fast Keys HART 7 Fast Keys
2-wire offset sensor 1 2, 2, 1, 5 2, 2, 1, 6
2-wire offset sensor 2 2, 2, 2, 5 2, 2, 2, 6
Alarm values 2, 2, 5, 6 2, 2, 5, 6
Analog calibration 3, 4, 5 3, 4, 5
Analog output 2, 2, 5 2, 2, 5
Average temperature setup 2, 2, 3, 3 2, 2, 3, 3
Burst mode N/A 2, 2, 8, 4
Comm status N/A 1, 2
Configure additional messages N/A 2, 2, 8, 7
Configure Hot Backup
2, 2, 4, 1, 3 2, 2, 4, 1, 3
Date 2, 2, 7, 1, 2 2, 2, 7, 1, 3
Descriptor 2, 2, 7, 1, 3 2, 2, 7, 1, 4
Device information 2, 2, 7, 1 2, 2, 7, 1
Differential temperature setup 2, 2, 3, 1 2, 2, 3, 1
Filter 50/60 Hz 2, 2, 7, 5, 1 2, 2, 7, 5, 1
Find device N/A 3, 4, 6, 2
First good temperature setup 2, 2, 3, 2 2, 2, 3, 2
Hardware revision 1, 8, 2, 3 1, 11, 2, 3
HART lock N/A 2, 2, 9, 2
Intermittent sensor detect 2, 2, 7, 5, 2 2, 2, 7, 5, 2
Lock status N/A 1, 11, 3, 7
Long tag N/A 2, 2, 7, 2
Quick Start Guide March 2021
8 Rosemount 3144P