June 2016
22
Quick Start Guide
7.5 USA
E5 Explosionproof (XP), Dust-Ignitionproof (DIP)
Certificate: FM 3020497
Standards: FM Class 3600 – 2011; FM Class 3610 – 2010; FM Class 3611 – 2004;
FM Class 3615 – 2006; FM Class 3810 – 2005; ANSI/ISA 60079-0 – 2013;
ANSI/ISA 60079-11 – 2012; ANSI/NEMA 250 – 2003
Markings: XP CL I, DIV 1, GP B, C, D; DIP CLII/III, DIV 1, GP E, F, G; T4 Ta=60°C and 70°C;
Type 4X
Special Conditions for Safe Use (X):
1. Potential Electrostatic Charging Hazard – The enclosure contains non-metallic material.
To prevent the risk for electrostatic sparking the plastic surface should only be cleaned
with a damp cloth.
2. WARNING – The apparatus enclosure contains aluminum and is considered to
constitute a potential risk of ignition by impact or friction. Care must be taken into
account during installation and use to prevent impact or friction.
I5 Intrinsic Safety (IS), Nonincendive (NI)
Certificate: FM 3020497
Standards: FM Class 3600 – 2011; FM Class 3610 – 2010; FM Class 3611 – 2004; FM
Class 3615 – 2006; FM Class 3810 – 2005; ANSI/ISA 60079-0 – 2013;
ANSI/ISA 60079-11 – 2012; ANSI/NEMA 250 – 2003;
Markings: IS CL I, II, III, DIV 1, GP A, B, C, D, E, F, G in accordance with control drawing
9150079-905; IS (Entity) CL I, Zone 0, AEx ia IIC T4 in accordance with
control drawing 9150079-905, NI CL I, II, DIV 2, GP A, B, C, D, F, G; Suitable
for use in CL III DIV 2, indoor and outdoor, T4 Ta=60 °C and 70°C; Type 4X
Special Conditions for Safe Use (X):
1. Potential Electrostatic Charging Hazard - The enclosure contains non-metallic material.
To prevent the risk for electrostatic sparking the plastic surface should only be cleaned
with a damp cloth.
2. WARNING - The apparatus enclosure contains aluminum and is considered to constitute
a potential risk of ignition by impact or friction. Care must be taken into account during
installation and use to prevent impact or friction.
IE FISCO
Certificate: FM 302049
Standards: FM Class 3600 – 2011; FM Class 3610 – 2010; FM Class 3611 – 2004;
FM Class 3615 – 2006; FM Class 3810 – 2005; ANSI/ISA 60079-0 – 2013;
ANSI/ISA 60079-11 – 2012; ANSI/NEMA 250 – 2003;
Markings: IS CL I, II, III, DIV 1, GP A, B, C, D, E, F, G in accordance with control drawing
9150079-905; IS (Entity) CL I, Zone 0, AEx ia IIC T4 in accordance with
control drawing 9150079-905, NI CL I, II, DIV 2, GP A, B, C, D, F, G; Suitable
for use in CL III DIV 2, indoor and outdoor, T4 Ta=60 °C and 70°C; Type 4X
Special Conditions for Safe Use (X):
1. Potential Electrostatic Charging Hazard – The enclosure contains non-metallic material.
To prevent the risk for electrostatic sparking the plastic surface should only be cleaned
with a damp cloth.
Ui Ii Pi Ci Li
Entity parameters HART
30 V 130 mA 1 W 7.26 nF 0
Entity parameters Fieldbus
30 V 300 mA 1.3 W 0 0