Quick Start Guide
41
August 2015
Approvals Document
July 24, 2015
08732-AP01, Rev AF
Canadian Standards Association (CSA)
CLASS 2258 02 - PROCESS CONTROL EQUIPMENT - For Hazardous Locations – To Canadian Requirements.
N6 Class I, Groups A, B, C and D (Intrinsically Safe Output and Electrode circuit)
N6 Class I, Division 2, Groups A, B, C and D (Non-Incendive)
N6 Class II, Division 1, Groups E, F and G (Dust Ignition Proof)
Magnetic Flow Meter – Model 8732EM Transmitter with integral or remote mount to Model 8705M or Model
8711M/L Magnetic Flow Tubes. Enclosure Type 4X and IP 66 Rated.
For Remote Mount Configuration – Temperature Code T4 with an Ambient Operating Temperature Range: -40°C
чdĂчнϲϬΣǁŝƚŚŽƌǁŝƚŚŽƵƚ>ŵĞƚĞƌǁŝƚŚŽƌǁŝƚŚŽƵƚĚŝŐŝƚĂů/KĂŶĚŽƌƉƵůƐĞŽƵƚƉƵƚƐǁŚĞŶŝŶƐƚĂůůĞĚƉĞƌ
Rosemount Drawing 08732-2061.
For Integral Mount Configuration – Ambient Operating Temperature Range: -29°C чdĂчнϲϬΣ. Temperature
Code T3-T6 dependent on line size of Flow Tubes for Process Temperature. The T-Code is defined as per
Rosemount Drawing 08705-00CS and 08732-00CS for ‘N6’ option or ‘KU’ option.
CLASS 2258 82 - PROCESS CONTROL EQUIPMENT - For Hazardous Locations –To US Requirements
KU Class I, Division 1, Groups C and D (Explosion Proof)
N6, KU Class I, Groups A, B, C and D (Intrinsically Safe Output and Electrode circuit
N6, KU Class I, Division 2, Groups A, B, C and D (Non-Incendive)
N6, KU Class II, Division 1, Groups E, F and G (Dust Ignition Proof)
Magnetic Flow Meter – Model 8732EM Transmitter with integral or remote mount to Model 8705M or Model
8711M/L Magnetic Flow Tubes. Enclosure Type 4X and IP 66 Rated.
For Remote Mount Configuration – Temperature Code T6 for Explosion Proof, T5 for Dust Ignition Proof, and T4
for Non-Incendive. Ambient Operating Temperature Range: -ϰϬΣчdĂчнϲϬΣǁŝƚŚŽƌǁŝƚŚŽƵƚ>ŵĞƚĞƌǁŝƚŚ
or without digital I/O and/or pulse outputs when installed per Rosemount Drawing 08732-2061.
For Integral Mount Configuration – Ambient Operating Temperature Range: -ϮϵΣч dĂчнϲϬΣ. Temperature
Code T3-T6 dependent on line size of Flow Tubes for Process Temperature. The T-Code is defined as per
Rosemount Drawing 08705-00CS and 08732-00CS for ‘N6’ option or ‘KU’ option.
Special Conditions of Safe Use:
1. For use with the appropriate 8705M and 8711M/L Flow tubes only.
2. When the 8732EM transmitter is integrally mounted to 8705M or 8711M/L Flow Tubes, the ambient
temperature ranges marked on each product need to be taken into consideration before installation.
The Ambient temperature range for 8732EM transmitter is -ϰϬΣчdĂчнϲϬΣĂŶĚƚŚĞĂŵďŝĞŶƚ
temperature range for 8705M or 8711M/L Flow Tubes is -ϮϵΣчdĂчнϲϬΣ Therefore, the -29°C rating
of the flow tubes will limit the overall cold temperature range of the complete system unless other
approved temperature control methods are employed.