Unidrive M300/HS30 Quick Start Guide 31
Issue Number: 6
Set Pr 00.004 at the required rate of deceleration. Note that larger values produce lower 
deceleration. The rate applies in both directions of rotation.
Use Pr 00.005 to select the required frequency/speed reference as follows:
00.004 {02.021} Deceleration Rate 1
RW Num US
OL
Ú
±VM_ACCEL_RATE s/100 Hz
Ö
10.0 s/100 Hz
RFC-A
00.005 {11.034} Drive Configuration 
RW Txt PT US
OL
Ú
AV (0), AI (1), AV.Pr (2), AI.Pr (3),
Preset (4), Pad (5), Pad.Ref (6), 
E.Pot (7), torque (8), Pid (9)
Ö
AV (0)
Value Text Description
0AV
Analog input 1 (voltage) Analog input 2 (voltage) selected by terminal 
(Local/Remote)
1AI
Analog input 1 (current) or Analog input 2 (voltage) selected by terminal 
(Local/Remote)
2AV.Pr
Analog input 1 (voltage) or 3 presets selected by terminal
3 AI.Pr
Analog input 1 (current) or 3 presets selected by terminal
4Preset
Four presets selected by terminal
5Pad
Keypad reference
6 Pad.Ref
Keypad reference with terminal control
7E.Pot
Electronic Potentiometer
8 torque
Torque mode, Analog input 1 (current frequency reference) or Analog input 2 
(voltage torque reference) selected by terminal
9Pid
PID mode, Analog input 1 (current feedback source) and Analog input 2 
(voltage reference source)
A change to Pr 00.005 is set by pressing the MODE key on exit from parameter edit mode. 
The drive must be disabled, stopped or tripped for a change to take place. If Pr 00.005 is 
changed while the drive is running, when the MODE key is pressed on exit from parameter 
edit mode, Pr 00.005 will change back to its previous value.
When the setting of Pr 00.005 is changed, the appropriate drive configuration parameters 
are set back to their default values.
Unidrive M300 Quick Start Guide English Iss6.book  Page 31  Tuesday, September 22, 2015  3:21 PM