Unidrive M300/HS30 Quick Start Guide 57
Issue Number: 6
10.10 Group installation
10.10.1 Definition
Group Installation Definition: A motor branch circuit for two or more motors, or one or more motors
with other loads, protected by a circuit breaker or a single set of fuses.
10.10.2 Limitations on use
All motors rated less than 1 hp
The drives may be used in group installations where each of the motors is rated 1 hp or less. The full-
load current rating of each motor must not exceed 6 A. The motor drive provides individual overload
protection in accordance with the NEC clause 430.32.
Smallest motor protected
The drives may be used in group installations where the smallest motor is protected by the branch
fuses or circuit breaker. Limits on the current rating of branch circuit protective fuses and circuit
breakers are given in the NEC Table: 430.52.
Other installations
The motor drives described in this user guide are not UL listed for group installation.
10.11 UL listed accessories
The following options are UL listed:
AI-485 Adaptor
AI-Backup Adaptor
Remote Keypad
UL Type 1 kit
NV Media card
SI-PROFIBUS
SI-DeviceNet
SI-CANopen
SI-EtherNet
SI-EtherCAT
SI-I/O
Unidrive M300 Quick Start Guide English Iss6.book Page 57 Tuesday, September 22, 2015 3:21 PM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Unidrive HS30 and is the answer not in the manual?

Emerson Unidrive HS30 Specifications

General IconGeneral
BrandEmerson
ModelUnidrive HS30
CategoryController
LanguageEnglish

Related product manuals