EasyManua.ls Logo

Emerson Unidrive HS30 - Page 39

Emerson Unidrive HS30
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Unidrive M300/HS30 Quick Start Guide 39
Issue Number: 6
Defines the functionality of Analog Output 1.
Defines the maximum switching frequency that can be used by the drive.
See the Drive User Guide for drive derating data.
00.036 {07.055} Analog Output 1 Control
RW Txt US
OL
Ú
0 to 14
Ö
0
RFC-A
Value Description
0 User defined by Analog Output 1 Source A
1 Frequency output
2 Frequency reference
3 Motor speed
4 Current Magnitude
6 Torque output
7 Torque current output
8 Voltage output
9 DC bus voltage (0~800 V)
10 Analog Input 1
11 Analog Input 2
12 Power output (0~2 x Pe)
13 Torque limitation
14 Torque reference (0~300 %)
00.037 {05.018} Maximum Switching Frequency
RW Txt US
OL
Ú
0.667 (0), 1 (1), 2 (2), 3 (3), 4 (4),
6 (5), 8 (6), 12 (7), 16 (8) kHz
Ö
3 (3) kHz
RFC-A
2 (2), 3 (3), 4 (4), 6 (5), 8 (6), 12 (7),
16 (8) kHz
Pr 00.037 Text Description
0 0.667 667 Hz switching frequency
1 1 1 kHz switching frequency
2 2 2 kHz switching frequency
3 3 3 kHz switching frequency
4 4 4 kHz switching frequency
5 6 6 kHz switching frequency
6 8 8 kHz switching frequency
7 12 12 kHz switching frequency
8 16 16 kHz switching frequency
Unidrive M300 Quick Start Guide English Iss6.book Page 39 Tuesday, September 22, 2015 3:21 PM