52 Unidrive M300/HS30 Quick Start Guide
Issue Number: 6
So.St
Soft start relay failed to close, soft 
start monitor failed
Soft start relay in the drive failed to close or the soft start 
monitoring circuit has failed.
St.HF
Hardware trip has occurred during 
last power down
Hardware trip (HF01 –HF19) has occurred and the drive has 
been power cycled. Enter 1299 to xx.000 to clear trip
Sto No Safe Torque Off board installed Safe Torque Off board not installed.
th Motor thermistor over-temperature
The motor thermistor connected to terminal 14 (digital input 5) 
on the control connections has indicated a motor over 
temperature.
th.br Brake resistor over temperature
The th.br trip is initiated if the hardware based braking resistor 
thermal monitoring is connected and the resistor overheats.
tH.Fb Internal thermistor has failed Internal thermistor has failed.
thS Motor thermistor short circuit
The motor thermistor connected to terminal 14 (digital input 5) 
on the control connections, is short circuit or low impedance 
(<50 Ω).
tun.S
Autotune test stopped before 
completion
The drive was prevented from completing an autotune test, 
because either the drive enable or the drive run signals were 
removed.
tunE.1 Autotune 1
The drive has tripped during a rotating autotune. The cause of 
the trip can be identified from the sub-trip number.
Refer to the Drive User Guide.
tunE.3 Autotune 3
RFC-A mode only.
The drive has tripped during a rotating auto-tune or mechanical 
load measurement. The cause of the trip can be identified from 
the associated sub-trip number.
Refer to the Drive User Guide.
U.OI User OI ac
The U.OI trip is initiated if the output current of the drive exceeds
the trip level set by User Over Current Trip Level. Refer to the
Drive User Guide.
U.S User Save error / not completed
The U.S trip indicates that an error has been detected in the 
user save parameters saved in non-volatile memory. 
US.24
User 24 V supply is not present on 
the adaptor interface terminals 
(1,2)
A US.24 trip is initiated if the User Supply Select is set to 1 and 
no user 24 V supply is present on the user 24 V input on the AI-
Backup adaptor. Refer to the Drive User Guide.
Trip 
code
Condition Description
Sub-trip Reason
1 Reserved
2
The motor did not reach the required 
speed during rotating auto-tune or 
mechanical load measurement.
Sub-trip Reason
1
Measured inertia has exceeded the 
parameter range during a mechanical 
load measurement.
2 Reserved
3
The commutation signals changed in 
the wrong direction during a rotating 
autotune.
Unidrive M300 Quick Start Guide English Iss6.book  Page 52  Tuesday, September 22, 2015  3:21 PM