60  Unidrive M100 / M101 Control User Guide
       Issue Number: 1
Figure 10-4 Menu 3 Logic diagram
Parameter
Range
 (Ú) Default (Ö)
Type
OL OL
03.001 Final Demand Reference VM_FREQ Hz
RO Num ND NC PT FI
03.005 Zero Frequency Threshold 0.00 to 20.00 Hz 2.00 Hz RW Num US
03.006 At Frequency Lower Limit 0.00 to 550.00 Hz 1.00 Hz RW Num US
03.007 At Frequency Upper Limit 0.00 to 550.00 Hz 1.00 Hz RW Num US
03.008 Over Frequency Threshold 0.00 to 550.00 Hz 0.00 Hz RW Num US
03.009 Absolute At Frequency Select Off (0) or On (1) Off (0) RW Bit US
03.022 Hard Frequency Reference VM_SPEED_FREQ_REF Hz 0.00 Hz RW Num US
03.023 Hard Frequency Reference Select Off (0) or On (1) Off (0) RW Bit US
03.037
Frequency Output or PWM Output
Scaling (T10)
0.000 to 4.000 1.000 RW Num US
03.038 Maximum Output Frequency (T10) 1 (0), 2 (1), 5 (2), 10 (3) kHz 5 (2) kHz RW Txt US
03.072 Motor Speed Percent ±150.0 %
RO ND NC PT FI
RW Read / Write RO Read only Num Number parameter  Bit Bit parameter Txt Text string Bin Binary parameter FI Filtered
ND No default value NC Not copied PT Protected parameter RA Rating dependent US User save PS Power-down save DE Destination
Date Date parameter Time Time parameter
mm.ppp
mm.ppp
Key
Read-write (RW)
parameter
Read-only (RO)
parameter
Input
terminals
Output
terminals
The parameters are all shown in their default settings
T 10 Digital
I/O1
03.037
??.???
??.???
At Zero
Frequency
10.003
Any valid
parameter
Maximum Output
Frequency
T10 Digital I/O01
Output Select
Frequency Output or
PWM Output Scaling
T10 DO1 Control
T10 DI/O Source /
Destination B
T10 Digital IO1
Source / Destination A
08.091
08.021
≥1
03.038
08.031
2or3
0to1
10
08.121