EasyManua.ls Logo

Emerson Unidrive M100 - Page 83

Emerson Unidrive M100
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Basic
parameters
Running the
motor
Optimization NV Media Card
Advanced
parameters
Diagnostics UL Listing
Unidrive M100 / M101 Control User Guide 83
Issue Number: 1
d.Ch Drive parameters are being changed
97
A user action or a file system write is active that is changing the drive parameters and the drive has been commanded to
enable, i.e. Drive Active (10.002) = 1.
Recommended actions:
Ensure the drive is not enabled when defaults are being loaded
dEr.E Derivative file error
246
Derivative file error with sub-trips:
Recommended actions:
Contact the supplier of the drive.
Trip Diagnosis
Sub-trip Reason Comments
1 The derivative file is missing or is invalid
Occurs when the drive powers-up. Load valid derivative file
matching the control board hardware.
2
The derivative file does not match the
control board hardware
Occurs when the drive powers-up. Load valid derivative file
matching the control board hardware.
3
The derivative file has been changed for a
file with a different derivative number.
Occurs when the drive powers-up or the file is
programmed. The file tasks will not run.

Table of Contents

Other manuals for Emerson Unidrive M100